ABB i-bus EIB/KNX AA/S 4.1 Product Manual page 14

Analogue actuator,analogue actuator module. intelligent installation systems
Table of Contents

Advertisement

ABB i-bus
EIB / KNX
®
12
Commissioning
Factor of input value
Options:
– Input value * 0,01
– Input value * 0,1
– Input value * 1
– Input value * 10
– Input value * 100
With the three parameters "Input value for 0 %", "Input value for 100 %" and
"Factor of input value" the output curve of the actuator can be matched to
different input variables.
Both input values should be selected to ensure that the smallest possible
factor can cover the required range to assure the best possible internal
resolution.
Output value after initialisation in %
Options:
– 0...100 (0)
Independent of the size of the input objects, the output value during an
initialisation is defined with this parameter, for example after reprogramming
or bus voltage failure.
Response to bus voltage failure
Options:
– last value
– output value in %
If the supply voltage is present, the output can either retain the last value or
set the output to a new value with a bus voltage failure.
Output value in %: If this option is selected the parameter "Output value in
%" is displayed.
Output value in %:
Options:
– 0...100 (0)
For setting the output value in % with bus voltage failure.
Response on return of bus voltage
Options:
– no response
– state of initialization
– state as before bus voltage failure
When the bus voltage recovers the output can retain its current value,
apply the set initialisation value or can restore the state as before bus
voltage failure.
Input object request on new start
Options:
– no
– yes
Yes: The output sends a read request to its sending group address.
The value which has been received is then set as the output value.

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bus eib/knx aam/s 4.1

Table of Contents