Installation

Observe these guidelines when installing a field controller:
Transport the controller in the original container to minimize vibration and shock damage.
Verify that all parts shipped with the controller.
Do not drop the controller or subject it to physical shock.

Parts Included

one field controller with removable terminal blocks
one installation instructions sheet

Materials and Special Tools Needed

three fasteners appropriate for the mounting surface (M4 screws or #8 screws)
one 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only)
small straight-blade screwdriver for securing wires in the terminal blocks
Mounting
Observe these guidelines when mounting a field controller:
Ensure the mounting surface can support the controller, DIN rail, and any user-supplied enclosure.
Mount the controller horizontally on 35 mm DIN rail whenever possible.
Mount the controller in the proper mounting position
Mount the controller on a hard, even surface whenever possible in wall-mount applications.
Use shims or washers to mount the controller securely and evenly on the mounting surface.
Mount the controller in an area free of corrosive vapors and observe the Ambient Conditions requirements in
Table
10.
Provide for sufficient space around the controller for cable and wire connections for easy cover removal and
good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
Do not mount the controller on surfaces prone to vibration, such as duct work.
Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can interfere
with controller communication.
Observe these additional guidelines when mounting a controller in a panel or enclosure:
Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the controller.
Mount the controller so that the power transformer and other devices do not radiate excessive heat to the
controller.
Do not install the controller in an airtight enclosure.
FEC1611 and FEC1621 Field Equipment Controller Installation Instructions
(Figure
1).
2

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FEC1611 and is the answer not in the manual?

This manual is also suitable for:

Fec1621

Table of Contents