Commissioning (Optional Equipment Settings); Ewg 01.1 Electronic Position Transmitter - AUMA SA 07.2 Operation Instructions Manual

Multi-turn actuators with actuator controls
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

Commissioning (optional equipment settings)

10.
Commissioning (optional equipment settings)
10.1.

EWG 01.1 electronic position transmitter

Technical data
Setting elements
46
EWG 01.1 electronic position transmitter signals the remote position or the valve
position. On the basis of the actual valve position sensed by hall sensor, a current
signal between 0
20 mA or 4
Table 16: EWG 01.1
Data
Output current I
a
1)
Power supply U
V
Max. current consumption
Max. load R
B
Impact of power supply
Load influence
Temperature impact
2)
Ambient temperature
1)
Power supply possible via: AC, AM actuator controls or external power supply
2)
Depending on temperature range of the actuator: Refer to name plate
The EWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
All settings are made via the two push buttons [S1] and [S2].
Figure 38: View on control unit when switch compartment is open
[S1]
Push button: Set 0/4 mA
[S2]
Push button: Set 20 mA
LED Optical aid for setting
[1]
Measuring point (+) 0/4
[2]
Measuring point ( ) 0/4
The output current (measuring range 0 20 mA) can be checked at measuring points
[1] and [2].
Table 17:
Short overview on push button functions
Push but-
Function
tons
[S1] + [S2]
→ press simultaneously for 5 s: Activate setting mode
[S1]
→ press in setting mode for 3 s: Set 4 mA
→ press in setting mode for 6 s: Set 0 mA
→ press in operation for 3 s: Switch on/off LED end position signalling.
→ touch in end position: Reduce current value by 0.02 mA
[S2]
→ press in setting mode for 3 s: Set 20 mA
→ press in operation for 3 s: Switch on/off LED end position signalling.
→ touch in end position: Increase current value by 0.02 mA
SA 07.2
SA 16.2 /SAR 07.2
20 mA is generated.
3-wire and 4-wire systems
0
20 mA, 4
20 mA
24 V DC (18
32 V)
LED off = 26 mA, LED on = 27 mA
600 Ω
< 0.1 ‰/K
60 °C to +80 °C
20 mA
20 mA
SAR 16.2
AM 01.1/AM 02.1
2-wire system
4
20 mA
24 V DC (18
32 V)
20 mA
(U
12 V)/20 mA
V
0.1 %
0.1 %