Complete Operating Menu / Description
Switching direction
Limit value 1; Limit value 2
Switch-on delay ∆t on
Switch-off delay ∆t off
If the limit is exceeded for longer than the "Delay time - limit values" an error message is given, which
must be acknowledged, and the alarm relay circuit is broken. If "Controller" is also set to "off" the control
process stops.
Servomotor
The operating range is defined by the total resistance range of the feedback potentiometer. The maximum
limit of the range actually used is set by defining the control range.
CAUTION
• Activation of the servomotor must be carried out with the same meticulous care as taken
when calibrating a measuring probe.
• To ensure correct operation, the activation time of the actuator used should not be less
than 25 seconds for the control range from 0...100 %!
Access to all setting menus can be blocked with an access code !
Only with servomotor
servomotor
setting ?
Possible values
Initial value
Increment
active closed active closed
active open
0 s
1 s
0 s
1 s
servomotor
setting
current position:
servomotor
OK
current position:
Lower value
Upper value
0 s
9999 s
0 s
9999 s
servomotor
open ?
servomotor
close ?
dosing:
ClO
2
control range:
0 % to
100 %
operating range
Remarks
Acts as N/O
Acts as N/C
servomotor
open
please wait !
servomotor
opened !
value take over ?
servomotor
close
please wait !
servomotor
closed !
value take over ?
= automatic timing
D1C2-ClO2-025-GB