baltur TBL 210P Original Instructions Manual page 54

Double-stage diesel burners
Table of Contents

Advertisement

Available languages

Available languages

ENGLISH
TBL 85 - 105 ..
GRAVITY SUPPLY SYSTEM
1
2
9
5
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
1
10
7
9
6
Value P = 3.5 m (Max)
INTAKE SUPPLY SYSTEM
7
1
10
1
Serbatoio
2
Feeding pipe
3
Mesh filter
4
Pompa
5
Degasificatore
H
4
Meters
7
1
6
1,5
2
8
3
2,5
3
1
Serbatoio
3
Mesh filter
4
Pompa
6
Suction pipe
H
4
Meters
1
1,5
2
8
3
2,5
3
1
Serbatoio
3
Mesh filter
4
Pompa
4
Meters
6
3
N.B. Comply with the regulations in force for any components missing in the
pipelines.
H = Difference in level between minimum level in tank and pump axis
L = Deduct 0.25 m for each elbow or gate.
14 / 38
0006081053_201805
6
7
8
9
Total L.
Meters
Øi 14 mm
30
35
35
40
40
7
8
9
10
Total L.
Meters
Øi 14 mm
30
35
35
40
40
6
7
10
H
Øi 14 mm
0,5
26
1
22
1,5
19
2
14
2,5
11
Suction pipe
Burner return pipe
Automatic shut-off device with
burner off
Unidirectional valve
Return pipe
Automatic shut-off device with
burner off
Unidirectional valve
Foot valve
Suction pipe
Return pipe
Foot valve
Total L.
Meters
Øi 16 mm
45
38
31
25
19

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Tbl 85pTbl 85p dacaTbl 105pTbl 260pTbl 130pTbl 105p daca ... Show all