Page 1
IT - GB - SP - FR - Istruzioni per bruciatori modello TBL 85P TBL 85P DACA - Instruction for burners model TBL 105P TBL 105P DACA - Instrucciónes para quemadores modelos - Mode d’emploi bruleûr TBL 130P TBL 130P DACA TBL 160P...
Page 3
P r i m a d i i n i z i a r e a u s a r e i l b r u c i a t o r e l e g g e r e a t t e n t a m e n t e q u a n t o e s p o s t o n e l l ’ o u s c o l o “AVVERTENZE PER L’UTENTE, PER L’USO IN SICUREZZA DEL BRUCIATORE”...
Page 4
Statement of Conformity We hereby declare under our own responsibility, that our “CE” marked products Series: Sparkgas…; BTG…; BGN…; TBG...; Minicomist…; Comist…; RiNOx…, BT…; BTL…; TBL...; GI…; GI…Mist; PYR…; TS… Description: domestic and industrial blown air burners fired by gas, oil and dual fuel respect the minimal regulation of the European Directives: •...
• If there is any fault or if the equipment is not working properly, de-activate the equipment and do not attempt to repair it or tamper with it directly. In such case get in touch with only qualified technicians. Any product repairs must only be carried out by BALTUR authorised assistance centres using only original spare parts.
WARNING NOTES FOR THE USER HOW TO USE THE BURNER SAFELY ELECTRICAL SUPPLY • The equipment is electrically safe only when it is correctly connected to an efficient ground connection carried out in accordance with current safety regulations. It is necessary to check this essential safety requirement. If in doubt, call for a careful electrical check by a qualified technicians, since the manufacturer will not be liable for any damage caused by a poor ground connection.
REV.: 16/01/08 TBL 85P/ P DACA - TBL 105P/ P DACA - TBL 130P/ P DACA - TBL 160P/ P DACA -TBL 210P TWO STAGE The working fields are obtained from test boilers corresponding to the standard EN267 and are indicatively for the combination burner- boiler.
Page 10
PIPES FOR LIGHT OIL BURNERS MODEL TBL 85P/ P DACA - 105P/ P DACA GRAVITY SUPPLY SYSTEM 1 Tank 6 Suction pipe 2 Feeding pipe 7 Return pipe 3 Wire-net filter 8 Automatic fuel interception 4 Pump device at burner shut off 5 Degasifier 9 Non-return valve Total meters...
Page 11
PIPES FOR LIGHT OIL BURNER MODEL TBL 130P/ P DACA - 160P/ P DACA - 210P GRAVITY SUPPLY SYSTEM 1 Tank 7 Return pipe 2 Feeding pipe 8 Automatic fuel interception 3 Wire-net filter device at burner shut off 4 Pump 9 Non-return valve 5 Degasifier 6 Suction pipe...
LEGEND Note Pressure loss: TBL 85P - 85P DACA = 1 bar 1 - Foot valve TBL 105P - 105P DACA = 1,5 bar 2 - Eventual air regulation motor TBL 130P - 130P DACA = 1,5 bar 3 - 2 flame nozzle...
Page 13
APPLICATION OF BURNER TO BOILER HEAD UNIT ASSEMNLY A) Adjust the position of connector flange 5 by loosening the screws 6 so that the combustion head penetrates the advised amount into the combustion chamber as recommended by the generator’s manufacturer. B) Position the seal insulation 3 on the tube unit inserting cord 2 between flange and seal.
ELECTRICAL CONNECTIONS The three-phase power supply line must have a switch with fuses. The regulations further require a switch on the burner’s power supply line, outside the boiler room and in an easily accessed po- sition. For the electrical connections (line and thermostats), follow the wiring diagram enclosed.
Page 15
The control equipment follows the program and switches the ignition DESCRIPTION OF WORKING transformer off. When the temperature or the pressure in the boiler reaches that set by the thermostat or pressure switch, the latter stops N.B. the burner. Subsequently, when the temperature or the pressure falls It is not advisable to have too large a burner for the boiler for heating and below the closing level of that of the thermostat or pressure switch, the for hot water as the burner may work for long periods with a single flame,...
with a boiler mounting flange, which slides in respect to the FIRST FILLING UP OF PIPELINES combustion head. After making sure that protective plastic caps inside the pump fittings f) The nozzles fitted on the burner should match the boiler have been removed, proceed as follows : capacity but, if necessary, replace them with others.
Page 17
CHECKS After starting up the burner, check the safety devices (photoresistance, block, thermostats). 1) The photocell is the flame control device and so it should trip if the flame extinguishes during operation (this check should be made after at least 1 minute from lighting up). The burner should be capable of blocking itself and remain so when a normal flame does not come on during start-up cycle and within the preset on control box.
Page 18
N.B. To prevent damage to the support effect nozzle assembly/disassembly tasks with the aid of a wrench and counter- wrench. RECOMENDED NOZZLES MONAMRCH tipo PLP 60° (TBL 85P) MONARCH tipo PLP 60° (TBL 105P) MONARCH tipo PLP 60° (TBL 130P) STEINEN tipo SS 45° (TBL 160P) STEINEN tipo SS 45° (TBL 210P) N.B.
MAINTENANCE Carry out periodic analysis of the exhaust combustion gas, che- cking the emissions. Periodically replace the light oil filter when dirty. Check that all the components of the combustion head are in a good state, not deformed by the temperature and free from im- purities or deposits from the installation environment or by poor combustion and check also the electrodes are working efficiently.
Page 21
HOW TO FIND THE CAUSES OF IMPROPER WORKING OF BURNERS USING TWO-STAGE LIGHT OIL AND HOW TO RECTIFY THEM TYPE OF IRREGULARITY POSSIBLE CAUSE REMEDY 1) Clean or replace it The burner goes to lock-out with the flame on 1) Photoresistance severed or fouled with smoke 2) Check all the smoke ducts in the boiler and (Red lamp on).
Page 22
HOW TO FIND THE CAUSES OF IMPROPER WORKING OF BURNERS USING TWO-STAGE LIGHT OIL AND HOW TO RECTIFY THEM TYPE OF IRREGULARITY POSSIBLE CAUSE REMEDY 1) Re-set it at the required rating Defective flame with sparks 1) Atomizing pressure too low 2) Reduce combustion air flow 2) Too much combustion air 3) Clean it or replace it...
Page 23
DETAILS OF SUNTEC PUMP AN 47 - 57 - 67 - 77 - 97 AJ4 - AJ6 8894-1 0002900331 rev.05/04/96 rev. 05/04/96 1 ELECTROVALVE (USUALLY CLOSED) 4.1 WAY-BACKWITH SCREW OF INNER BY-PASS 2 PRESSURE TEST POINT AND PUR 5 SUCTION GE POINT (1/8”...
Page 31
Il presente catalogo riveste carattere puramente indicativo. La casa, pertanto, si riserva ogni possibilità di modifica dei dati tecnici e quant’altro in esso riportato. Technical data in this brochure are given as information only. Baltur reserves the right to change specification, without notice.
Need help?
Do you have a question about the TBL 105P and is the answer not in the manual?