Consider Housing Rotation - Emerson Rosemount MultiVariable 3051S Series Quick Start Manual

Flow meter transmitters
Hide thumbs Also See for Rosemount MultiVariable 3051S Series:
Table of Contents

Advertisement

October 2018
2

Consider housing rotation

About this task
To improve field access to wiring or to better view the optional LCD display:
Procedure
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° left or right of its original (as shipped)
position.
3. Re-tighten the housing rotation set screw.
Figure 2-1: Transmitter Housing Set Screw
Do not rotate the housing more than 180° without first performing a
disassembly procedure (refer to
information). Over-rotation may sever the electrical connection
between the sensor module and the electronics.
Quick Start Guide
A. LCD display
B. Housing rotation set screw (3/32-in.)
CAUTION
Troubleshooting
for more
Quick Start Guide
9

Advertisement

Table of Contents
loading

Table of Contents