In-Line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located under the sensor module neck label (see
Keep the vent path free of any obstruction, including but not limited to paint,
dust, and lubrication by mounting the transmitter so that any contaminants can
drain away.
Figure 4. In-Line Gage Transmitter
A
A. Low side pressure port (under neck label)
Step 2: Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° left or right of its original (as shipped) position.
3. Re-tighten the housing rotation set screw.
Figure 5. Transmitter Housing Set Screw
B
A. LCD display
B. Housing rotation set screw (3/32-in.)
Note
Do not rotate the housing more than 180° without first performing a disassembly procedure (refer
to the Rosemount 4088 MultiVariable Transmitter Reference Manual [00809-0100-4088] for more
information). Over-rotation may sever the electrical connection between the sensor module and
the electronics.
8
A
November 2014