Danfoss VLT HVAC Drive Instruction Manual page 95

Hide thumbs Also See for VLT HVAC Drive:
Table of Contents

Advertisement

VLT
®
HVAC Drive Instruction Manual
22-62
Value:
0 - 600 s
Function:
Sets the time during which the broken belt
conditions must be active before carrying out
the action selected in
par. 22-60.
22-75
Value:
Disabled
Enabled
Function:
Disabled
Starts
, par. 22-76 is disabled.
Enabled
Starts
, par. 22-76 is enabled.
22-76
Value:
0 - 3,600 s
Function:
Sets the time desired as minimum time be-
tween two starts. Any normal start command
(Start/Jog/Freeze) will be disregarded until
the timer has expired.
22-77
Value:
0 - par. 22-76
Function:
Sets the time desired as min. run time after a
normal start command (Start/Jog/Freeze).
Any normal stop command will be disregarded
until the set time has expired. The timer will
Broken Belt Delay
Broken Belt Function,
Short Cycle Protection
Interval Between
[0]: Timer set in
Interval between
[1]: Timer set in
Interval Between Starts
Minimum Run Time
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
6. How to program the adjustable frequency
start counting after a normal start command
(Start/Jog/Freeze).
The timer will be overridden by a coast (in-
verse) or an external interlock command.
10 s
[0]
[1]
0 s
0 s
drive
6
95