Line Power Wiring Overview - Danfoss VLT HVAC Drive Instruction Manual

Hide thumbs Also See for VLT HVAC Drive:
Table of Contents

Advertisement

4. Electrical installation
4.1.3. Grounding and IT line power
The power supply is connected to the main disconnect switch if this is included.
4

4.1.4. Line power wiring overview

Please refer to the following table for the line power wiring connection instructions.
Enclo-
sure:
Motor
size:
200-240 V
380-480 V
525-600 V
Goto:
Table 4.5: Line power wiring table.
30
The ground connection cable cross-section must be at least 0.016 in.
2 rated line power wires terminated separately according to
61800-5-1
, unless national regulations specify otherwise. Always comply with na-
tional and local regulations on cable cross-sections.
NOTE
Make sure that the line voltage corresponds to the line voltage of the adjustable
frequency drive nameplate.
IT Line
Do not connect 400 V adjustable
frequency drives with RFI filters
to line supplies with a voltage
between phase and ground of
more than 440 V.
For IT lines and delta ground
(grounded leg), line voltage
may exceed 440 V between
phase and ground.
A2
A3
(IP 20/IP
(IP 20/IP
(IP 55/IP
21)
21)
66)
1.1-3.0
3.7
1.1-3.7
kW
kW
kW
1.1-4.0
5.5-7.5
1.1-7.5
kW
kW
kW
2.2-4.0
5.5-7.5
kW
kW
4.1.5
4.1.6
MG.11.A4.22 - VLT
VLT
Illustration 4.1: Terminals for line supply and
grounding.
A5
B1
B2
(IP 21/IP
(IP 21/IP
55/IP 66)
55/IP 66)
5.5-11
15
kW
kW
11-18.5
22-30
kW
kW
4.1.7
®
is a registered Danfoss trademark
®
HVAC Drive Instruction Manual