Fuse Specifications - Danfoss VLT FC 102 Operating Instructions Manual

1.1-90 kw hvac drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Specifications

8.8 Fuse Specifications

It is recommended to use fuses and/or circuit breakers on the supply side as protection in case of component break-down
inside the frequency converter (first fault).
NOTICE
This is mandatory in order to ensure compliance with IEC 60364 for CE or NEC 2009 for UL.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), depending on the
frequency converter voltage rating. With the proper fusing the frequency converter Short Circuit Current Rating (SCCR) is
100,000 Arms.
8.8.1 CE Compliance
200-240 V
Enclosure
type
A2
A3
8
8
B3
B4
C3
C4
A4
A5
B1
B2
C1
C2
Table 8.11 200-240 V, Enclosure Types A, B and C
56
Power [kW]
Recommended
fuse size
1.1-2.2
gG-10 (1.1-1.5)
gG-16 (2.2)
3.0-3.7
gG-16 (3)
gG-20 (3.7)
5.5-11
gG-25 (5.5-7.5)
gG-32 (11)
15-18
gG-50 (15)
gG-63 (18)
22-30
gG-80 (22)
aR-125 (30)
37-45
aR-160 (37)
aR-200 (45)
1.1-2.2
gG-10 (1.1-1.5)
gG-16 (2.2)
0.25-3.7
gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
5.5-11
gG-25 (5.5)
gG-32 (7.5-11)
15
gG-50
18-30
gG-63 (18.5)
gG-80 (22)
gG-100 (30)
37-45
aR-160 (37)
aR-200 (45)
®
VLT
HVAC Drive Operating Instructions
Recommended
Max. fuse size
gG-25
gG-32
gG-63
gG-125
gG-150 (22)
aR-160 (30)
aR-200 (37)
aR-250 (45)
gG-32
gG-32
gG-80
gG-100
gG-160 (18.5-22)
aR-160 (30)
aR-200 (37)
aR-250 (45)
MG11AJ02 - Rev. 2013-07-31
Recommended circuit
Max. trip level [A]
breaker (Moeller)
PKZM0-25
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
25
25
50
100
150
250
25
25
63
100
160
250

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 102 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents