Ir Area Settings - Omron SYSMAC C200H-NC111 Operation Manual

Position control unit
Hide thumbs Also See for SYSMAC C200H-NC111:
Table of Contents

Advertisement

Manual Operations
HIGH-SPEED JOG Speed
Number
LOW-SPEED JOG
Speed Number
4–9–2

IR Area Settings

HIGH-SPEED JOG
Command
JOG Direction
LOW-SPEED JOG
Command
INCH Command
SpeedsDM words m+82 through m+96
Speed Units
DM word m+97
Acceleration
Bits 11-00 of DM word m+98
Deceleration
Bits 11-00 of DM word m+99
word m+1, bits 15-12
Set an integer between 1 and F (hex).
The speed number set here refers to one of the speeds set in DM words
m+82 through m+96.
word m+1, bits 11-08
Set an integer between 1 and F (hex).
The speed number set here refers to one of the speeds set in DM words
m+82 through m+96.
In C200H PCs, IR words 100 to 199 are used for Special I/O Units. When a
Position Control Unit is used, they are allocated as I/O refresh areas. For a
detailed explanation, see 3–4 Data Configuration and Allocation. For a de-
tailed table of words and bits in the IR area, see Appendix D IR Area Alloca-
tions.
word n, bit 11
0:
Stop
1:
Operate
word n, bit 12:
0:
CW
1:
CCW
word n, bit 13
0:
Stop
1:
Operate
word n, bit 14
0:
Stop
1:
Operate
Section 4–9
79

Advertisement

Table of Contents
loading

Table of Contents