AEMC DTR 8510 User Manual page 36

Digital transformer ratiometer
Table of Contents

Advertisement

1. Connect the Primary (H) cable to the appropriate connectors on
the DTR
Model 8510 and the transformer under test. Connect the
®
Secondary (X) cable as a loop through the current transformer hole as
shown in the figure.
2. Press the TEST button. During the Ratio test, the instrument will
check for H/X reverse polarity, short (excessive current) etc. before
conducting Ratio test.
NOTE:
• If the H/X is reversed, the instrument will display the error
message (see Fig. 5-5) as in VT/PT test and terminate the test.
• If there were a polarity reversal, the Ratio would be blinking with
a negative sign. This means either the connections are reversed
on a given side or the transformer is wound backwards relative
to the marking.
• The test can be cancelled at any time by pressing the TEST
button during the operation.
• The CT test ramps up the voltage in steps. At the end of the test,
it ramps down the voltage.
• There are certain low mass, low ratio CT's for which the DTR
8510 may not be able to provide correct ratio. The error message
will be "High Excitation Current".