• The Present Nameplate values are displayed in the Main
Screen.
• Each Measurement Record will record the Present Nameplate
along with other associated parameters and will be available
when the data is downloaded.
• The Ratio of the nameplate values must be between 1 and
32767.
• The Nameplate needs to be enabled. If the Nameplate is
not enabled, the Deviation % will not be reported after the
measurements. Subsequently, the stored values will not have
Nameplate and Deviation % in the Measurement Record.
NOTE: The Main Screen will display the Present Nameplate only if
it is Enabled. If it is not Enabled, it will display "---" for Primary and
Secondary.
To configure the settings for the Nameplate, perform the following:
1. Within the top level of Configure Instrument, press the ▼ or ▲ key
until Setup Nameplate appears on the display, then press ENTER.
2. The display will show Enable with Yes and No choices. Press the ▼
key to select Yes (Enable Nameplate).
18
Shop for AEMC products online at:
Figure 4-9
Figure 4-10
Digital Transformer Ratiometer DTR
ShopAEMC
www.
Model 8510
®
.com