If the H/X were reversed, the instrument will display the following error
message and terminate the test.
NOTE:
• If there were a polarity reversal, the Ratio would be displayed
negative and it would be blinking. This means either the
connections are reversed on a given side or the transformer is
wound backwards relative to the marking.
• The test may be run as many times as needed by pressing the
TEST button.
• An active test can be cancelled at any time by pressing the
TEST button.
• Make sure that the H
does not short to the X
earth ground. See § 6 for more connection details.
5.2.2

Storing the Measurement Record

The storage mode you are in depends on what you selected when config-
uring the instrument (see § 4.3) before running a test.

5.2.2.1 Manual Mode

When Manual mode is selected, the Measurement Record storage is
optional to the user.
1. To store the active measurement using Manual mode, press the MEM
(ENTER) button. The display looks as shown below:
Digital Transformer Ratiometer DTR
Shop for AEMC products online at:
Figure 5-5
lead is always connected such that it
RED
or X
RED
Figure 5-6
Model 8510
®
ShopAEMC
www.
lead directly or through
BLACK
(Manual and Auto Mode)
.com
1.877.766.5412
31