Technical Data - Siemens SINAMICS DCM Operating Instructions Manual

Commutation reactors
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Technical data

General technical specifications
Degree of protection
Safety class
Cooling
Inductance tolerance
Environmental classes according to
DIN IEC 60721-3 Parts 1 to 3
Ambient Temperature during Operation
• 1-phase reactors
• 3-phase reactors
Ambient temperature
storage and transport
Installation altitude
(at rated current)
Operation at 50 Hz and 60 Hz with rated current is permissible
Note
Declaration for protection class 1
Despite protective conductor connection, no 'touchable conductive parts' with regard to the
standard (e.g. EN 61800-5-1) are defined.
In this case, the protective conductor ensures that no dangerous voltages/currents can act at
the mounting surfaces.
The complete reactor must be considered as being an active part.
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B
IP00
Class 1 (see also note below)
AN, self-ventilated
±10 %
Climatic:
Storage
Transport
Operation
Mechanical:
0 to +45° C, above with derating
0 to +40° C, above with derating
-40° to +70° C
≤ 1000 m above sea level, above with
derating
6
1K3
2K2
3K3
3M3
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents