Siemens SINAMICS DCM Operating Instructions Manual page 31

Commutation reactors
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Table 6- 4
Commutating reactors 3ph
uk=4 % for rated current and 3AC 690 V/50 Hz or 3AC 830 V/60 Hz
Order
AC rated
number
current
6RX1800-..
4KK00
598 A
4KK01
631 A
4KK02
789 A
4KK03
830 A
4KK04
1245 A
4KK05
1577 A
4KK06
1660 A
4KK07
2158 A
Table 6- 5
Commutating reactors 3ph
uk=4 % for rated current and 3AC 830 V/50 Hz or 3AC 950 V/60 Hz
Order
AC rated
number
current
6RX1800-..
4LK00
789 A
4LK01
1245 A
4LK02
1577 A
4LK03
1826 A
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B
DC rated
Inductance Copper
current
losses
720 A
0.085 mH 388.2 W
760 A
0.080 mH 402.0 W
950 A
0.064 mH 362.7 W
1000 A
0.061 mH 350.7 W
1500 A
0.041 mH 505.2 W
1900 A
0.032 mH 716.8 W
2000 A
0.031 mH 596.0 W
2600 A
0.024 mH 484.8 W
DC rated
Inductance Copper
current
losses
950 A
0.077 mH 312.0 W
1500 A
0.049 mH 692.4 W
1900 A
0.039 mH 479.4 W
2200 A
0.033 mH 585.6 W
Total
SCCR
Weight
losses
562.1 W
55 kA
108.9 kg
(200 ms)
586.4 W
75 kA
113.3 kg
(200 ms)
564.6 W
75 kA
141.9 kg
(200 ms)
561.4 W
75 kA
153.4 kg
(200 ms)
845.7 W
75 kA
169.7 kg
(200 ms)
1093.8 W
75 kA
226.1 kg
(200 ms)
1011.8 W
75 kA
257.2 kg
(200 ms)
1185.6 W
75 kA
360.2 kg
(200 ms)
Total
SCCR
Weight
losses
532.1 W
75 kA
205.2 kg
(200 ms)
1061.9 W
75 kA
222.4 kg
(200 ms)
1059.6 W
75 kA
308.5 kg
(200 ms)
1269.0 W
75 kA
372.5 kg
(200 ms)
Technical data
Rated
Insulating
insulating
material
voltage
class
according
to
DIN EN
60085
1000 V
F
1000 V
F
1000 V
F
1000 V
F
1000 V
F
1000 V
F
1000 V
F
1000 V
F
Rated
Insulating
insulating
material
voltage
class
according
to
DIN EN
60085
1000 V
F
1000 V
F
1000 V
F
1000 V
F