Operating the positioner

7.10 Enabling and selecting parameters

All codes and their meaning and default settings are listed in the code list in section 11.4.
Codes which are marked with an asterisk must be enabled with Code 3 before the associat-
ed parameters can be configured as described below.
Turn
until Code 3 appears (reading: No).
Press
, the code number 3 blinks.
Change the setting in Code 3.
Turn
until YES appears.
Press
, reading:
Configuration is enabled.
You can now configure codes one after the
other:
Turn
to select the required code.
Press
to activate the selected code. The
code number starts to blink.
Turn
to select the setting.
Press
to confirm the selected setting.
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid and the display returns to Code 0.
Cancel the setting:
To cancel a value before it is confirmed (by pressing
Turn
until ESC appears.
Press
to confirm.
The entered value is not adopted.
120
Code 3
Configuration not en-
abled
Configuration enabled
) proceed as follows:
Canceling the reading
EB 8384-6 EN