8

Operation

WARNING!
The actuator stem moves while the positioner
is being operated.
Do not touch the actuator stem or obstruct it
to avoid risk of injury to hands or fingers.
8.1
Enabling and selecting
parameters
The codes which are marked with an aster-
isk (*) in section 14 on page 74 onwards
must be enabled with Code 3 before the as-
sociated parameters can be configured as
described below.
Turn
® Code 3, display: No
Press
, Code 3 blinks.
Change the setting of Code 3 .
Turn
® YES
Press
, display:
The configuration is enabled.
Code 3
Configuration
not enabled
Configuration
enabled
You can now configure codes one after the
other:
Turn
and select the required code.
Press
to access the selected code. The
code number starts to blink.
Turn
and select the setting.
Press
to confirm the selected setting.
Note: If no settings are entered within 120
seconds, the enabled configuration function
becomes invalid and the display changes to
Code 0.
Cancel the setting:
To cancel a value before it is confirmed (by
pressing
) proceed as follows:
® ESC
Turn
Press
. The entered value is not adopted.
Operation
Canceling the setting
EB 8384-5 EN