Enable configuration:
Configuration is locked again if no settings are entered within 120 s.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Setting the bus address:
1. Turn
until Code 46 appears.
2. Press
, the code number 46 blinks.
3. Turn
and select the desired bus address.
4. Press
and hold for 10 seconds.
The address is adopted straightaway, provided that cyclic data exchange is not taking place.
During the cyclic data exchange, the newly set address for the positioner is saved and adopt-
ed after the cyclic data exchange is completed. The newly assigned address is indicated in
Code 46 in alternating sequence with the current address. The new address is marked with
'n' (new) and the currently used address with 'o' (old).
Note
The bus address can only be implemented by the PROFIBUS command SET_ADDRESS when
the bus address is set to the default setting [126]. Refer to Configuration Manual
u KH 8384-4.

7.12 Enabling and selecting parameters

All codes and their meaning and default settings are listed in the code list in section 11.3.
Codes which are marked with an asterisk must be enabled with Code 3 before the associat-
ed parameters can be configured as described below.
EB 8384-4 EN
Operating the positioner
Enable configuration
Default: No
Default: 126