Enabling And Selecting Parameters - Samson 3730-4 Mounting And Operating Instructions

Series 3730 electropneumatic positioner
Table of Contents

Advertisement

Operation
4.2
Enabling and selecting
parameters
The codes which are marked with an aster-
isk (*) in section 14.1 on page 110 onwards
must be enabled with Code 3 before the as-
sociated parameters can be configured as
described below.
4
From the current display, turn the rotary
pushbutton until Code 3 and OFF ap-
pear on the display.
Confirm Code 3 by pressing the
ton, the code number blinks.
4
Turn
button until ON appears.
Confirm setting by pressing the
ton.
Configuration is enabled and is indicated by
symbol appearing on the display.
Now you can adjust the codes, parameters
and values for the control valve in any de-
sired order by turning the
firm settings by pressing the
46
EB 8384-4 EN
Code 3
Configuration
not enabled
Configuration
enabled
but-
but-
button. Con-
button.
Important!
To cancel a value that you have just entered
under a code, turn the
appears on the display and press to con-
firm.
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid and the display re-
sets to Code 0.
The code list in section 14.1 on page 110
onwards shows all parameters that can be
adjusted, including their description and
their default settings.
Important!
After attaching the positioner to the valve as
well as setting the fail-safe position and the
volume restriction, it is sufficient for standard
operation to press the initialization key in
order to ensure optimum positioner opera-
tion (section 5.6 on page 52).
For this purpose, the positioner must be op-
erated with its default values. If necessary, a
reset must be carried out (section 5.9 on
page 61).
button until ESC
Canceling the setting