Program Options
Printer Installed (04)
The factory default entry of '0' in address 04 informs the FACP that a printer is not connected to the panel. This
entry must be changed to '1' if a printer is connected. The PRT-24 printer interface module must be installed on J4
of the MS-5210UD main circuit board before a printer can be installed.
Printer Baud Rate (05)
Address 05 is used to set the Baud Rate when a printer is connected to the MS-5210UD. The factory default entry
is '0' for 2400 Baud. Enter '1' for 4800 Baud or '2' for 9600 Baud. An entry in address 05 is valid only if a printer
has been enabled in address 04.
NAC/Relay Option Module (06)
A Notification Appliance Circuit/Relay Option (NAC-REM) Module is available which adds two Style Z
(Class A) NAC circuits (NACs 3 and 4) and two programmable Form-C relays (Relays 3 and 4). The factory
default setting for address 06 is '0' for no module installed. This entry must be changed to '1' if the NAC/Relay
module is installed.
Programmable Relay 3 Definition (07)
This address programs Relay 3 if the NAC/Relay Option Module has been enabled in address 06. The factory
default entry for Relay 3 is '1' for supervisory. Enter '0' for alarm; '2' for supervisory autoresettable; '3' for trouble;
'4' for communication fail; '5' for process monitoring; '6' for autoresettable process monitoring.
Programmable Relay 4 Definition (08)
This address programs Relay 4 if the NAC/Relay Option Module has been enabled in address 06. The factory
default entry for Relay 4 is '4' for communication fail. Enter '0' for alarm; '1' for supervisory; '2' for supervisory
autoresettable; '3' for trouble; '5' for process monitoring; '6' for autoresettable process monitoring.
NAC #3 Type Selection (09)
This address programs NAC #3 if the NAC/Relay Option Module has been enabled in address 06. The factory
default entry for NAC #3 is '0' for enabled and silenceable. Enter '1' for enabled and nonsilenceable or '2' for dis-
abled.
NAC #3 Silence Inhibit (10)
This address is used for the silence inhibit feature on NAC #3 if the NAC/Relay Option Module has been enabled
in address 06. The factory default entry for NAC #3 is '0' for no silence inhibit. Enter '1' to enable the silence
inhibit feature for NAC #3. This will prevent the silencing of NAC #3 for one minute following activation of an
alarm.
NAC #3 Autosilence (11)
This address is used for the autosilence feature on NAC #3 if the NAC/Relay Option Module has been enabled in
address 06. The factory default entry for NAC #3 is '0' for no autosilence. If you wish NAC #3 to be automati-
cally silenced after one of the following lengths of time (requires prior approval of Local AHJ), enter '1' for 5 min-
utes; '2' for 10 minutes; '3' for 15 minutes; '4' for 20 minutes; '5' for 25 minutes; or '6' for 30 minutes.
NAC #3 Signal Coding (12)
This address is used to select coding for NAC #3 if the NAC/Relay Option Module has been enabled in address
06. The factory default entry for NAC #3 is '0' for steady output (no coding). Enter '1' for March Time coding
(120 ppm); '2' for California Time coding (10 secs. On, 5 secs. Off); or '3' for Temporal Time coding (½ sec. On, ½
sec. Off, ½ sec. On, ½ sec. Off, ½ sec. On, 1½ secs. Off, and then repeat sequence).
NAC #4 Type Selection (13)
This address programs NAC #4 if the NAC/Relay Option Module has been enabled in address 06. The factory
default entry for NAC #4 is '0' for enabled and silenceable. Enter '1' for enabled and nonsilenceable or '2' for
disabled.
Document #50193
Rev. E
01/30/02
P/N 50193:E
61