Program Options
Enter the remaining numbers in their respective addresses as shown below:
Entry
Address
Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as
dialed numbers and the hexadecimal digits representing the following functions:
• A = * on a Touch-Tone phone keypad
• B = # on a Touch-Tone phone keypad
• C = look for secondary dial tone for up to two seconds (then dial anyway)
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must be entered in all unused phone number locations)
Primary Central Station Number Communication Format (16)
One location is needed to select the Communication Format to the primary phone number. Address 16 is used for
this purpose. The default ( factory setting) for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
Note: Consult you Central Station for proper selection or consult our factory representatives. For any format cho-
sen, the control panel automatically programs all of the event codes. See Table 3-3 through Table 3-8 .
!
CAUTION: Default entries for event codes (as shown in Table 3-3 through Table 3-8 ) are programmed into mem-
ory each time address '16' is altered. Be certain to double check entries after programming the zone functions,
addresses 64 - 73. Program the format first, then program the zone(s) function. Do not alter while the communi-
cator is active.
Primary Central Station Number Account Code (17-20)
The four locations at addresses 17-20 default to all '0s'. Valid entries are 0-9 and A-F. The number of digits
entered must match the format selection. If programming '2, 3, 4 or 5' into address 16, enter three digits (one digit
each in locations 17, 18 and 19 - location 20 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into
address 16, enter four digits (one digit each in locations 17, 18, 19 and 20).
4
8
4
7
1
6
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Document #50193
1
F
F
F
F
F
F
Rev. E
01/30/02
P/N 50193:E
F
F
F
41