Program Options
Make/Break Ratio for Primary Phone (59)
Use this address only if you have chosen '1' for address 58. The Make/Break ratio is factory set to '0' which is 67/
33 ratio, but may be changed to '1' which is 62/38 ratio.
Touchtone/Rotary Select for Secondary Phone (60)
A '0' programmed in this address by the factory triggers Touchtone dialing over the secondary phone line. Select
'1' for rotary dialing.
Make/Break Ratio for Secondary Phone (61)
Use this address only if you have chosen '1' for address 60. The Make/Break ratio is factory set to '0' which is 67/
33 ratio, but may be changed to '1' which is a 62/38 ratio.
Address (62)
Leave entry as default of '0'.
Address (63)
Leave entry as default of '0'.
Zones 1 through 10 Function Selection (64-73)
The ten zones on the control panel may be programmed as shown in Table 3-1 . Program entries alter zone func-
tion, transmittal priority and, as a result of altering the zone definition, the transmitted event code message is auto-
matically changed. Remote switch entries 9, A, B and C cause the zone function to be altered to match the FACP
keypad entries. Initial closure (or shorting) of a switch causes the switch function to occur. The switch must be
returned to its normal position.
Zone Functions
TABLE 3-1:
Program Entry
0
1
2
3
4
5
6
7
8
9
A
B
C
1. For remote switch applications, use Fire•Lite P/N: AKS-1F or equivalent UL listed switch.
Zone 1 Function Selection (64)
Factory default for zone 1 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
44
Operate 2-wire smoke detectors
Pull Station
Normally-Open Contact Device (heat detector, 4-wire smoke, etc.)
Supervisory
Supervisory, autoresettable. Self restore function, is not latched by the control panel
Waterflow, silenceable. Silencing of Silenceable Notification Appliance Circuits allowed
Waterflow, nonsilenceable. Silencing of Silenceable Notification Appliance Circuits not
allowed. Must clear waterflow alarm condition and press reset key
Critical and noncritical process monitoring
Autoresettable process monitoring
1
Remote reset switch
1
Remote silence switch
1
Remote acknowledge switch
Remote manual evacuate (drill) switch
Document #50193
Function
1
Rev.E
01/30/02
P/N 50193:E