Option Modules Programming Sheets
Option Module Programming Reference Sheets Factory Defaults
---To enter Programming Level 3, press the MODE key, 7764, '3', [ENTER/STORE]
0
CAC-10F Class A Converter Card not installed.
0
0
LED-10IM EIA-485 Interface Module not installed. F
1
0
1
Maximum annunciator or ACM-8RF monitored address on EIA-485 line.
2
3
0
Printer not installed.
4
0
Printer Baud Rate. ('0' = 2400 Baud)
5
0
NAC/Relay Option Module not installed.
6
1
Programmable Relay #3 Definition. ('1' = supervisory).
7
4
Programmable Relay #4 Definition. ('4' = communication fail).
8
0
NAC #3 Type Selection. ('0' for NAC #3 enabled (silenceable).
9
0
NAC #3 Silence Inhibit. ('0' for no silence inhibit).
10
0
NAC #3 Autosilence feature which silences signals after a selected period. ('0' for no autosilence for NAC #3).
11
0
NAC #3 Signal Coding. ('0' for steady (no coding).
12
0
NAC #4 Type Selection. ('0' for NAC #4 enabled (silenceable).
13
0
NAC #4 Silence Inhibit. ('0' for no silence inhibit).
14
0
NAC #4 Autosilence feature which silences signals after a selected period. ('0' for no autosilence for NAC #4).
15
0
NAC #4 Signal Coding. ('0' for steady (no coding).
16
0
Non-Supervisory Annunciation.
17
Document #50193
Rev. E
01/30/02
P/N 50193:E
115