Optional Accessories
AFM-16ATF - The Annunciator Fixed Module-16ATF
contains 16 red alarm and 16 yellow trouble LEDs, a
system trouble LED, an ON LINE/POWER LED and a
local piezo sounder with switches for Acknowledge,
Silence, Reset and Drill. The AFM-16ATF is fixed at
address '1' and communication is via the EIA-485 data
line. The AFM-16ATF can be mounted in a Fire•Lite
ABS-1F or ABF-1F backbox. Refer to the AFM-16AT
Manual for detailed information.
AFM-16AF - The Annunciator Fixed Mod-
ule-16AF has 16 red alarm LEDs. Multiple
annunciators may be used by setting all annunci-
ators to Receive Only, except the last AFM-16AF
in line. Each annunciator's address is internally
fixed at '1' and communication is via the EIA-485
data line. The Local Silence/Acknowledge
switch functions as local lamp test and silence for
annunciator piezo. LEDs include On-Line and
System Trouble indicators. The AFM-16AF
Annunciator can be mounted in a standard 4-
gang electrical box. Refer to the AFM-16AF
Manual for detailed information.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander mod-
ules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power
and control for a maximum of three expander modules (expander modules are not required when interfacing to the
MS-5210UD). The LDM-32F and LDM-E32F have output connectors which are used to drive lamps or LEDs
and input connectors which are used for remote switch functions. The LDM Series requires the use of the
LED-10IM Interface Module. Refer to the LDM Series Lamp Driver Modules Manual for a complete description.
Refer to Figure 2-18, "Wiring LED-10IM to LDM-32F," on page 37 for wiring details.
LDM-32F - The Lamp Driver Module has 32
alarm lamp/LED driver outputs which sink cur-
rent to system common (-) on activation. A sin-
gle positive (+) voltage is required to supply total
operating power for all lamps or LEDs when all
drivers are activated. The LDM-32F provides a
separate driver for system trouble and inputs for
a local lamp test switch. A maximum of 16
external control switches may be wired to the
LDM-32F. DIP switch SW3 is used to enable or
disable the onboard piezo sounder, enable remote
switch functions, select a flashing LED function
for new alarms and troubles and other functions.
Switch SW4 is used to configure the module to
annunciate 32 alarms or 16 alarms and 16 trou-
bles. A green ON-LINE LED flashes to indicate
ongoing communications with the host FACP.
One LDM-32F supports up to three LDM-E32F
modules. The LDM-32F is supplied with four
standoffs and screws for mounting to a CHS-4L
chassis or custom backbox.
20
FIGURE 1-8:
FIGURE 1-10:
Document #50193
Rev.E
01/30/02
AFM-16ATF
AFM-16AF
FIGURE 1-9:
LDM-32F Module
P/N 50193:E