Program Options
Primary Central Station Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four
locations, from addresses 21-24. The default is 00:00 (12:00 midnight). The limits for each location are as fol-
lows (do not use values of A-F as entries):
21: enter 0, 1 or 2
22: enter 0-9
23: enter 0-5
24: enter 0-9
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (25)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter 1=12hr,
2=8hr or 3=6hr.
Secondary Central Station Phone Number (26-41)
Programming is similar to programming the primary phone number located at addresses 00 - 15. The defaults are
also all 'Fs'.
Entry
Address
Secondary Central Station Number Communication Format (42)
Programming is the same as the primary number's Communication Format at address 16. Default entry is 'E',
Contact ID Format. Choose one entry from the list below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2:3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format
chosen, the control panel automatically programs all of the event codes. See Table 3-3 through Table 3-8 .
CAUTION: Default entries for event codes (as shown in Table 3-3 through Table 3-8 ) are programmed into
!
memory each time address '42' is altered. Be certain to double check entries after programming the zone func-
tions, addresses 64 - 73. Program the format first, then program the zone(s) function. Do not alter entry while the
communicator is active.
42
F
F
F
F
F
F
26 27 28 29 30 31 32 33 34 35 36
Document #50193
F
F
F
F
F
F
37 38 39 40 41
Rev.E
01/30/02
P/N 50193:E