Program Options
Ademco Contact ID Format
If 'E' is entered for address 16 in Program Mode Level 1, the data shown in Table 3-5 is automatically pro-
grammed for the Primary Central Station phone number event codes. Enter '000' for the setting to disable the
report. The Setting entry is programmable, the Zone Number cannot be changed. Restoral code settings match
the settings shown with the addition of an 'R' code transmitted. Refer to page 109 for additional information.
Event Codes, Primary Central Station Number
TABLE 3-5:
Address
0-2
3-5
6-8
9-11
12-14
15-17
18-20
21-23
24-26
27-29
30-32
33-35
36-38
39-41
42-44
45-47
48-50
51-53
54-56
57-59
60-62
63-65
66-68
69-71
72-74
75-77
78-80
81-83
84-86
87-89
90-92
93-95
96-98
99-101
102-104
105-107
108-110
111-113
114-116
117-119
120-122
123-125
126-128
129-131
132-134
135-137
138-140
141-143
144-146
147-149
150-152
153-155
156-158
159-161
162-164
165-167
168-170
1. Refer to Table 3-1 for list of zone alarm event codes.
54
Description
Primary # Zone 1 Alarm Code
Primary # Zone 2 Alarm Code
Primary # Zone 3 Alarm Code
Primary # Zone 4 Alarm Code
Primary # Zone 5 Alarm Code
Primary # Zone 6 Alarm Code
Primary # Zone 7 Alarm Code
Primary # Zone 8 Alarm Code
Primary # Zone 9 Alarm Code
Primary # Zone 10 Alarm Code
Primary # Zone 1 Disabled Code
Primary # Zone 2 Disabled Code
Primary # Zone 3 Disabled Code
Primary # Zone 4 Disabled Code
Primary # Zone 5 Disabled Code
Primary # Zone 6 Disabled Code
Primary # Zone 7 Disabled Code
Primary # Zone 8 Disabled Code
Primary # Zone 9 Disabled Code
Primary # Zone 10 Disabled Code
Primary # Drill Code
Primary # AC Fault Code
Primary # Zone 1 Fault Code
Primary # Zone 2 Fault Code
Primary # Zone 3 Fault Code
Primary # Zone 4 Fault Code
Primary # Zone 5 Fault Code
Primary # Zone 6 Fault Code
Primary # Zone 7 Fault Code
Primary # Zone 8 Fault Code
Primary # Zone 9 Fault Code
Primary # Zone 10 Fault Code
Primary # Earth Fault Code
Primary # Low Battery Fault Code
Primary # No Battery Fault Code
Primary # Telco Primary Line Fault Code
Primary # Telco Secondary Line Fault Code
Primary # NAC #1 Fault Code
Primary # NAC #2 Fault Code
Primary # NAC #3 Fault Code
Primary # NAC #4 Fault Code
Primary # NAC #1 Disable Code
Primary # NAC #2 Disable Code
Primary # NAC #3 Disable Code
Primary # NAC #4 Disable Code
Primary # Comm Trouble Primary # Code
Primary # Comm Trouble Secondary # Code
Primary # Printer Fault Code
Primary # Annunciator Fault Code
Primary # 485 Comm Trouble Code
Primary # System Off Normal Code
Primary # System Test Message
Primary # System Abnormal Test Message
Primary # Upload/Download Request Code
Primary # Upload Successful Code
Primary # Download Successful Code
Primary # Upload/Download Failed Code
Document #50193
Setting
1
111
1
111
1
111
1
111
1
111
1
111
1
111
1
111
1
111
1
111
570
570
570
570
570
570
570
570
570
570
604
301
380
380
380
380
380
380
380
380
380
380
310
302
311
351
352
321
322
326
327
521
522
526
527
354
354
336
330
330
308
602
608
411
416
412
413
Rev.E
01/30/02
P/N 50193:E
Zone No.
001
002
003
004
005
006
007
008
009
010
001
002
003
004
005
006
007
008
009
010
000
000
001
002
003
004
005
006
007
008
009
010
000
000
000
000
000
001
002
003
004
001
002
003
004
001
002
000
001
002
000
000
000
000
000
000
000

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-5210ude

Table of Contents