Digital Communicator

Output Circuits
• 24 Volt Resettable Power Output 500 mA
• 24 Volt Nonresettable Power Output 500 mA
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger (up to 18 AH batteries)
• Printer Port
• EIA-485 Port (interfaces to LED-10 Annunciator, AFM Series and LDM Graphic Series Annunciators and
ACM-8RF Remote Relay Module)
Notification Appliance Circuits
Two Notification Appliance Circuits Style Y (Class B) configurable for Style Z (Class A) using the CAC-10F
option module.
Relays
Two dry Form-A relay contacts programmable for system alarm, system trouble, system supervisory (standard
and autoresettable), standard and autoresettable process monitoring or communications failure are provided.
Contacts are rated 2.0 amps @ 30 VDC (resistive). Two additional Form-C relay contacts programmable for
alarm, trouble, standard and autoresettable supervisory, standard and autoresettable process monitoring or com-
munications fail are available using the NAC-REM (NAC/Relay) option module. Contacts are rated 2.0 amps @
30 VDC and 0.6 amps at 125 VAC (resistive).
Printer Port
EIA-232 compatible, fully supervised and programmable for 2400, 4800 and 9600 Baud. Only one printer may
be connected to the port. Consult the factory for recommended printers.
EIA-485 Port
EIA-485 compatible port on the LED-10IM option module supports up to 32 LED-10 Remote Annunciators or 32
sets of ACM-8RF Relay Modules or 32 AFM Series Annunciators or 32 LDM Series Annunciators or any combi-
nation of the four devices totalling 32.
Telephone Lines
Fully supervised at all times, voltage is sensed to 4 volts and current is sensed to 5 mA.
Battery Charger
Battery Charger will charge up to 18 AH batteries. The MS-5210UD cabinet holds a maximum of 12 AH batter-
ies. The Fire•Lite BB-17F is required to hold 18 AH batteries. The charger is rated for 850 mA maximum cur-
rent.
1.5
Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the
Primary and Secondary phone lines. Telephone line 'Active' red LEDs are provided as well as a green 'Kissoff' LED.
The integral digital communicator provides the following functions:
• Line Seizure - takes control of the phone lines disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone network
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) number - default is Touch-Tone
• For tone burst or touchtone type formats: discern proper 'Ack' and 'Kissoff' tone(s) - the frequency and time
duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
16
©
, programmable to rotary
Document #50193
Rev.E
01/30/02
P/N 50193:E