Autosilence Notification Appliance Circuit #1 (82)
Notification Appliance Circuit #1 may be autosilenced after a programmed time interval between 5 and 30 min-
utes. Enter '1' for 5 minute autosilence; '2' for 10 minute autosilence; '3' for 15 minute autosilence; '4' for 20
minute autosilence; '5' for 25 minute autosilence; or '6' for 30 minute autosilence. The factory default is '0' for no
autosilence.
Coding of Notification Appliance Circuit #1 (83)
Coding of Notification Appliance Circuit #1 is selectable for the following: '1' for March Time (120ppm); '2' for
California (10 seconds On, 5 seconds Off); or '3' for Temporal ( ½ second On, ½ second Off, ½ second On, ½ sec-
ond Off, ½ second On, 1 ½ seconds Off and then repeat). Factory default is '0' for steady (no coding).
Notification Appliance Circuit #2 Enable (84)
Notification Appliance Circuit #2 may be programmed as '0' for silenceable, '1' for nonsilenceable or '2' for dis-
abled. Factory default is '0' for silenceable. Note: Consult the Local Authority Having Jurisdiction (LAHJ) prior
to altering this address.
Silence Inhibit Notification Appliance Circuit #2 (85)
Setting address 85 to '1' prohibits silencing of Notification Appliance Circuit #2 for one minute after initiation of
an alarm. Factory default is '0' for no silence inhibit of Notification Appliance Circuit #2.
Autosilence Notification Appliance Circuit #2 (86)
Notification Appliance Circuit #2 may be autosilenced after a programmed time interval between 5 and 30 min-
utes. Enter '1' for 5 minute autosilence; '2' for 10 minute autosilence; '3' for 15 minute autosilence; '4' for 20
minute autosilence; '5' for 25 minute autosilence; or '6' for 30 minute autosilence. The factory default is '0' for no
autosilence.
Coding of Notification Appliance Circuit #2 (87)
Coding of Notification Appliance Circuit #2 is selectable for the following: '1' for March Time (120ppm); '2' for
California (10 seconds On, 5 seconds Off); or '3' for Temporal ( ½ second On, ½ second Off, ½ second On, ½ sec-
ond Off, ½ second On, 1 ½ seconds Off and then repeat). Factory default is '0' for steady (no coding).
Trouble Reminder (88)
Factory default '0' disables the trouble reminder feature. Selecting '1' will cause a reminding beep (after the
Silence or Acknowledge switch is pressed) every 15 seconds during an alarm and beep every two minutes during
a trouble condition. The beeps from the onboard piezo sounder will occur until the alarm or fault is cleared.
Programming the Real-Time Clock and Calendar (89-999)
Entering an address greater than 88 will cause a display of the current time. On initial power-up, the clock will
start running from the factory setting of 00:01 (military time). The far left digit will be flashing, indicating that
this is the first digit to be programmed.
Note that the software for the MS-5210UD operates the internal clock based upon 60 Hz. The software for the
MS-5210UDE operates the internal clock based upon 50 Hz.
• Programming Hours and Minutes - To program the first hour digit, press the corresponding number on the
keypad and then press [ENTER/STORE]. For example, to program 08:00 AM, press '0' on the keypad and
then [ENTER/STORE]. The digit 2nd from the left will start flashing. Enter the second hour digit and press
[ENTER/STORE]. In the previous example, the number '8' would be pressed on the keypad followed by the
[ENTER/STORE] key. This completes the Hours setting. The digit 2nd from the right should now be flash-
ing on the display. Select the first digit for the minutes by pressing the corresponding number on the keypad
and then the [ENTER/STORE] key. The digit on the far right of the display will now be flashing. Select the
second digit for the minutes by pressing the corresponding number on the keypad and then the [ENTER/
STORE] key. The Minutes setting is now complete. If during programming of the time an invalid digit is
selected (i.e. 3 or higher for the first digit) the FACP piezo sounder will beep and the digit will continue to
blink until a valid entry is made.