Fire-Lite Alarms MS-5210UD Manual page 52

Fire alarm control panel
Table of Contents

Advertisement

Program Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' are entered for address 16 in Program Mode Level 1, the data shown in Table 3-4 is automatically
programmed for the Primary Central Station phone number event codes. Enter '00' for the setting to disable the
report.
Event Codes, Primary Central Station Number
TABLE 3-4:
Address
0-1
2-3
4-5
6-7
8-9
10-11
12-13
14-15
16-17
18-19
20-21
22-23
24-25
26-27
28-29
30-31
32-33
34-35
36-37
38-39
40-41
42-43
44-45
46-47
48-49
50-51
52-53
54-55
56-57
58-59
60-61
62-63
64-65
66-67
68-69
70-71
72-73
74-75
76-77
78-79
80-81
82-83
84-85
86-87
88-89
90-91
92-93
94-95
96-97
98-99
100-101
52
Description
Primary # Zone 1 Alarm Code
Primary # Zone 2 Alarm Code
Primary # Zone 3 Alarm Code
Primary # Zone 4 Alarm Code
Primary # Zone 5 Alarm Code
Primary # Zone 6 Alarm Code
Primary # Zone 7 Alarm Code
Primary # Zone 8 Alarm Code
Primary # Zone 9 Alarm Code
Primary # Zone 10 Alarm Code
Primary # Zone 1 Disabled Code
Primary # Zone 2 Disabled Code
Primary # Zone 3 Disabled Code
Primary # Zone 4 Disabled Code
Primary # Zone 5 Disabled Code
Primary # Zone 6 Disabled Code
Primary # Zone 7 Disabled Code
Primary # Zone 8 Disabled Code
Primary # Zone 9 Disabled Code
Primary # Zone 10 Disabled Code
Primary # Drill Code
Primary # AC Fault Code
Primary # Zone 1 Fault Code
Primary # Zone 2 Fault Code
Primary # Zone 3 Fault Code
Primary # Zone 4 Fault Code
Primary # Zone 5 Fault Code
Primary # Zone 6 Fault Code
Primary # Zone 7 Fault Code
Primary # Zone 8 Fault Code
Primary # Zone 9 Fault Code
Primary # Zone 10 Fault Code
Primary # Earth Fault Code
Primary # Low Battery Fault Code
Primary # No Battery Fault Code
Primary # Telco Primary Line Fault Code
Primary # Telco Secondary Line Fault Code
Primary # NAC #1 Fault Code
Primary # NAC #2 Fault Code
Primary # NAC #3 Fault Code
Primary # NAC #4 Fault Code
Primary # NAC #1 Disable Code
Primary # NAC #2 Disable Code
Primary # NAC #3 Disable Code
Primary # NAC #4 Disable Code
Primary # Comm Trouble Primary # Code
Primary # Comm Trouble Secondary # Code
Primary # Printer Fault Code
Primary # Annunciator Fault Code
Primary # 485 Comm Trouble Code
Primary # System Off Normal Code
Document #50193
Setting
1
11
1
12
1
13
1
14
1
15
1
16
1
17
1
18
1
19
1
1A
41
42
43
44
45
46
47
48
49
4A
97
92
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
61
62
63
64
65
66
67
68
69
4B
4C
4D
4E
6A
6B
6C
6D
6E
6F
Rev.E
01/30/02
P/N 50193:E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-5210ude

Table of Contents