Fire-Lite Alarms MS-5210UD Manual page 46

Fire alarm control panel
Table of Contents

Advertisement

Program Options
Zone 10 Function Selection (73)
Factory default for zone 10 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open con-
tact device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Note: Programming any zone to function as supervisory or supervisory autoresettable will cause the defaulted
zone alarm event codes (see note in Table 3-2 ) to be automatically changed. The defaulted code of '1' is changed
to '8' for formats 3+1 and 4+1 Standard and Expanded, 4+2 Expanded and 4+1 Express (refer to Table 3-3 and
Table 3-6 ). The defaulted codes of 11 through 1A are changed to 81 through 8A accordingly for formats 4+2
Standard and 4+2 Express (refer to Table 3-4 and Table 3-7 ). Programming any zone to function as process
monitoring (Zone Function Selections 7 or 8) will cause the alarm event code to be automatically programmed as
'0' or '00' which disables the report. Be certain to reprogram the alarm event code for each process monitoring
zone. Restoral codes remain unchanged from factory defaults.
When using Contact ID Format, zone alarm and zone restoral event codes change automatically as shown in
Table 3-2 . Be certain to reprogram alarm event codes when selecting process monitoring functions. Zone fault
and disable event codes may also be user programmed (refer to "Ademco Contact ID Format Event Code
Descriptions" on page 109).
Programming a zone as a remote switch causes no transmission of an alarm or alarm restoral event code. The
zone wiring continues to be supervised for opens whereas a short simulates closure of a reset, silence, drill or
acknowledge switch. Zone fault and zone restoral codes continue to be transmitted.
Event Code Changes for ID Contact Format
TABLE 3-2:
Zone Function Selection
0
1
2
3
4
5
6
7
8
9
A
B
C
Be certain to program appropriate process monitoring functions (refer to "Ademco Contact ID Format
1.
Event Code Descriptions" on page 109).
Waterflow Retard Timer (74-75)
A delay may be added prior to declaring a Waterflow type of alarm. Delays up to 89 seconds are allowed. The
default for addresses 74 and 75 are '00' (no additional delay). Valid entries for 74 are 0 through 8 and for 75 are 0
through 9. Program an entry into these addresses only if entering a '5' or '6' in any of the addresses 64 through 73.
Be careful to include any built-in delays of the waterflow device.
46
Function
2-wire Smoke
Pull Station
N.O. Contact Device
Supervisory
Autoresettable Supervisory
Waterflow (silenceable)
Waterflow (nonsilenceable)
Process Monitoring
Autoresettable Process Monitoring
Reset Switch
Silence Switch
Acknowledge Switch
Drill Switch
Document #50193
Zone Alarm/Restoral Event Code
111
115
110
200
200
113
113
000
000
N/A
N/A
N/A
N/A
Rev.E