How To Exit Walk Test™ Mode - Simplex 4100 Operator's Manual

Fire indicator panel
Hide thumbs Also See for 4100:
Table of Contents

Advertisement

Page 46
To enable multiple Walk Test™ groups, press the <NEXT> key to scroll to the next
Walk Test™ group. Then press the <F1> key to enable that group. Continue
scrolling, then press the >F1> key to select required Walk Test™ groups. Once all
Walk Test™ groups are selected, press the fault acknowledge key, then continue.
When a Walk Test™ group with no configured points is selected, the display shows
the following message.
No walk test points configured for:
WALK TEST GROUP X
Note: X equals 0 through 7.
7.9.3 How to Exit Walk Test™ Mode
When the Walk Test™ has been satisfactorily completed, exit from the Walk Test™
mode by performing the following procedure.
1.
Press the <MENU> key.
2.
Press the <NEXT> key to select the Walk Test™ function.
3.
Press the <ENTER> key.
4.
Press the <F1> key to turn off a Walk Test™ group. Press NEXT, then <F1>
to turn OFF each enabled Walk Test™ group.
Note: The system activates a one-minute timer when exiting from the Walk Test™
mode. This timer ensures that monitor points have had ample time to clear
(smoke) prior to enabling the system. After the one-minute delay, the system
Walk Test™ fault automatically clears.
5.
Press <MENU>. The Change Access Level menu is shown.
6.
Press <ENTER>.
7.
Press <F2> to log out.
8.
If Access Level 4 was entered, fault will continue to exist in the system.
Access Level 4 is normally used by Simplex personnel and additional steps
must be performed. Call Simplex to restore the system.
9.
Inform required personnel when system testing is completed.
Document No.: 4100-M001
SIMPLEX 4100 FIRE INDICATOR PANEL
28 March 2006
OPERATOR MANUAL
Issue 1.2