SIMPLEX 4100 FIRE INDICATOR PANEL
OPERATOR MANUAL

2 SYSTEM OPERATING DESCRIPTION

The 4100 Operator Interface Panel, shows the following under normal conditions:
*
Green "POWER ON" LED ON (indicating that AC power is applied).
*
All other interface panel indications OFF.
*
Alphanumeric display states that the SYSTEM IS NORMAL followed by
the time and date as shown below.
SIMPLEX AUSTRALIA SYSTEM IS NORMAL
08:23:43
Abnormal conditions are indicated on the 4100 panel by flashing the alarm, isolate,
or fault LED and sounding the tone-alert.
The alphanumeric display provides information as to the point status (alarm, isolated,
and fault), number of abnormal conditions in the system, and a custom label. Alarm,
isolate, and fault conditions each have their respective acknowledge key. Pressing
the appropriate acknowledge key will silence the tone-alert, however, the LED
indicating the abnormal condition remains illuminated until all initiating devices are
restored to normal. If your system is configured with a CRT or printer option, point
status is also displayed on these devices. The CRT option controls various system
f
unctions. It can also acknowledge sysm status changes and interrogate system
status.
Document No: 4100-M001
Figure 1
4100 Operator Interface Panel
(Panel Access Door Closed)
28 March 2006
MON 25 JAN 95
Page 3