How To Enable A Disabled Point - Simplex 4100 Operator's Manual

Fire indicator panel
Hide thumbs Also See for 4100:
Table of Contents

Advertisement

SIMPLEX 4100 FIRE INDICATOR PANEL
OPERATOR MANUAL
1.
Ensure the point to be turned AUTO is shown on the alphanumeric display. A
typical point (SIG2) is shown below.
MASTER SIGNAL POINT 2, SIG2
SIGNAL CIRCUIT
OFF
2.
Press the <AUTO> key. A typical display is shown below.
Press <ENTER> for AUTOmatic control
SIGNAL CIRCUIT: SIG2
3.
Press the <ENTER> key. A typical display is shown below.
MASTER SIGNAL POINT 2, SIG2
SIGNAL CIRCUIT
4.
Press the <CLR> key. The display shows the following message.

7.9.7 How to Enable a Disabled Point

If a device was disabled for any reason and has been restored, you can enable the
point. This point must first be identified to the system. The disabled point causes a
system fault condition which is continually shown on the alphanumeric display. This
can be viewed by pressing the fault <ACK> key and reading the alphanumeric
display. The point can be enabled by using the <ENABLE> key. If the <ENABLE>
key is passcode protected, perform Log In Procedures, then continue.
To enable a disabled point, perform the following procedures.
1.
Press the <FAULT ACK> key until the point to be enabled is shown on the
alphanumeric display, as shown in the following example.
MONITOR CARD 1
FIRE MONITOR ZONE
Document No: 4100-M001
OFF
SYSTEM IS NORMAL
9:27:40
MON 04-APR-96
ZONE NUMBER 12
28 March 2006
OFF
DISABLE FAULT
Page 49
Issue 1.2