Pressing the <ALARM ACK> key will:
A.
Acknowledge the displayed point or acknowledge all points on the list (Global
Acknowledge).
B.
Scroll the points chronologically after all points have been acknowledged.

3.2.2 System Reset

The <SYSTEM RESET> key is used to return the system to its normal state after an
alarm condition has been cleared. When the system reset key is pushed, it will
cause the latched circuits to clear
devices, relays, , indicating appliances, and all LEDs and indicators which are
programmed to reset with the reset key.
PROGRESS", will be displayed when the <SYSTEM RESET> key is pressed.
The <ALARM ACK> key is then pressed and the message "SYSTEM IS NORMAL",
followed by time and date should be displayed. This process will take about 45
seconds.
If a zone stays in alarm during the reset period, the message, "SYSTEM RESET IN
PROGRESS", will be followed by the message:
ALARMS = 1
When "SYSTEM RESET ABORTED" is displayed, the system will remain in an alarm
state. The display will indicate the total number of alarms present in the system
along with a prompt to use the <ALARM ACK> key to review the points. These
points do not require acknowledgment. The tone-alert and the alarm LED will be on.
If the system does not reset, no fire exists, and the display still shows an alarm, read
the alphanumeric display to determine type of device and the zone number in alarm.
Follow local procedures to investigate the area of the building with the alarm. Look
for devices still in alarm (manual call points, smoke detectors, etc.).
Document No.: 4100-M001
SIMPLEX 4100 FIRE INDICATOR PANEL
automatically.
ALARMS PRESENT
SYSTEM RESET ABORTED
OR
***ALARM*** Press <ACK> to review.
ISOLATED = 0
28 March 2006
OPERATOR MANUAL
All circuits include initiating
The message, "SYSTEM RESET IN
FAULT = 0
Issue 1.2