Chapter 6. Service Request Function
For the non-extended formats, the returned data for each fault consists of 21 words (42 bytes) for
00h and 01h and 23 words (46 bytes) for 41h. This request returns 16 Controller Fault Table entries
or 32 I/O Fault Table entries, or the actual number of faults, if fewer. If the fault table read is empty,
no data is returned.
The following tables show the return format of a Controller Fault Table entry and an I/O Fault Table
entry.
Format of Returned Data for Fault Table Entries
Format for Parameter Setting 00h or 01h
Controller Fault Table (00h) Output Format
High Byte
Unused
Unused
Slot
Task
Fault action
Error code
Fault extra data
Minutes
Day of month
Year
Start of next fault output parameter block
7
The Long/Short indicator in the low byte of
Fault Table
Controller
I/O
312
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual
Address
Low Byte
Long/short
Address+21
Unused
Address+22
Rack
Address+23
Address+24
Fault group
Address+25
Address+26
Address+27
Address+28
Address+29—
Address+38
Seconds
Address+39—
Address+41
Hour
(Time-stamp,
in BCD Format)
Month
Address+42
Address + 21
Long/Short Value
Fault Data Returned
00
8 bytes of fault extra data present in the fault entry
01
24 bytes of fault extra data
02
5 bytes of fault extra data
03
21 bytes of fault extra data
I/O Fault Table (01h) Output Format
High Byte
Memory type
Slot
Bus address
Fault action
Fault type
Fault extra data Fault description
Minutes
Day of month
Year
Start of next fault output parameter block
specifies the amount of fault data present in the fault entry:
Low Byte
Long/Short
7
Offset
Rack
I/O Bus Number (block)
Point
Fault group
Fault category
Fault extra data
Seconds
Hour
Month
GFK-2950C