Chapter 6. Service Request Function
SVC_REQ 56 Example
The following LD logic reads ten continuous bytes written to nonvolatile storage from %G1—%G80
into %G193—%G273. The value applied to IN1, 56, selects byte mode.
The parameter block starts at %R00040. The response words are returned to %R00049 and
%R00050.
Parameter Block for SVC_REQ 56 Example
Address + Offset
Address
Address+0
%R00040
Address+1
%R00041
Address+2
%R00042
Address+3
%R00043
Address+4
%R00044
Address+5
%R00045
Address+6
%R00046
Address+7
%R00047
Address+8
%R00048
Address+9
%R00049
Address+10
%R00050
334
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual
Input Value
Definition
56
Data type = %G (byte mode)
0
Address written from, low word
0
Address written from, high word
10
Length = 10 bytes
56
Data type to write to = %G (byte mode)
24
Address to write to, low word
0
Address to write to, high word
0
Storage disabled conditions are enforced
0
Reserved, must be set to 0
NA
Response status.
NA
Response count.
GFK-2950C