5.1

Circuit Breaker Failure (50BF)

The circuit breaker fail function has two time delayed outputs that can be used for combinations of
re-tripping or back-tripping. CB fail outputs are given after elapse of the 50BF-1 Delay or
50BF-2 Delay settings. The two timers run concurrently.
The circuit breaker fail protection time delays are initiated either from:
An output Trip Contact of the relay (MENU: OUTPUT CONFIG\TRIP CONFIG\Trip Contacts), or
A binary or virtual input assigned to 50BF Ext Trig (MENU: INPUT CONFIG\INPUT MATRIX\ 50BF Ext Trig).
A binary or virtual input assigned to 50BF Mech Trip (MENU: INPUT CONFIG\INPUT MATRIX\50BF Mech Trip).
CB fail outputs will be issued by providing any of the 3 phase currents are above the 50BF Setting or the current
in the fourth CT is above 50BF-I4 for longer than the 50BF-n Delay setting, or for a mechanical protection trip the
circuit breaker is still closed when the 50BF-n Delay setting has expired – indicating that the fault has not been
cleared.
Both 50BF-1 and 50BF-2 can be mapped to any output contact or LED.
If the CB Faulty input (MENU: INPUT CONFIG\INPUT MATRIX\CB Faulty) is energised when a CB trip is given
the time delays 50BF-n Delay will be by-passed and the output given immediately.
Operation of the CB Fail elements can be inhibited from:
Inhibit 50BF
50 BF Element
Enabled
Disabled
Inhibit 50BF
T rip Contact
≥1
50 BF Ext Trig
50 BF Mech Trip
&
CB Closed
50 BF Setting
IL1
>
IL2
IL3
50BF-I 4 Setting
IL4
>
Figure 5-1
©2018 Siemens Protection Devices Limited
A binary or virtual input.
50 BF CB Faulty
&
&
≥1
&
≥1
Logic Diagram: Circuit Breaker Fail Protection (50BF)
&
50BF- 1 Delay
&
50BF-2 Delay
&
7SR10 Description of Operation
≥1
50BF-1
≥1
50BF-2