General; Initial Inspection; Installation - Xantrex 6000 Series Technical Manual

Table of Contents

Advertisement

SECTION 2
INSTALLATION AND OPERATING INSTRUCTIONS
2.1 GENERAL
After unpacking,
an initial
inspection should
be performed
to
ensure that
the
unit
is
in
good
working
order.
If
it
is
determined that
the unit
is
damaged,
the
carrier
should
be
notified immediately.
Repair problems should be directed to the
Service Department, Xantrex Technology Inc.
2.2 INITIAL INSPECTION
The power
supply comes
complete with
an lEC power cord set and
technical manual. The equipment should be inspected for damage as
follows:
a.
Inspect panel
and chassis
for dents,
and
other
signs
of
obvious damage.
b.
Turn front panel controls from stop to stop.
Rotation should
be smooth.
c.
Test the
action of the power switch. Switching action should
be
positive.
d.
If internal
damage is
suspected, remove the cover and check
the
components
and
printed
circuit
board
for
damage.
Reinstall the cover.
2.3 INSTALLATION
Before connecting
the unit
to an
AC outlet, make sure that the
power switch
is
in the extended (OFF) position and the Voltage
and
Current
controls
are
in
their
fully
counter
clockwise
positions.
The AC line voltage should be 117V 60Hz nominal.
A voltage
control mode
indicator (green)
is located
above the
voltage control
knob.
A current limit mode indicator (red) is
located above
the current
limit
adjust knob.
The power supply
outputs are
red and black binding posts.
The green binding post
is connected to chassis and line ground.
Connect either
the (+)
or (-)
terminal" to
the ground terminal
depending upon
the desired output voltage polarity using a short
wire for
this connection.
If the output voltage is to be biased
relative to ground, it is recommended
that a O.OluF capacitor of
sufficient voltage
rating (200-1000V)
be used
in place
of the
shorting connection. The power supply outputs may be biased by up
to a maximum of +500Vdc with respect to line safety ground.
INSTALLATION & OPERATION