Tightness check liquid gas:
-Stabilisation time (0 - 60 min, default: 10 min)
-Measurement time (0 - 60 min, default: 10 min)
Test pressure (0 - 1000 hPa, default: 100 hPa)
Pressure test liquid gas:
-Stabilisation time (0 - 60 min, default: 10 min)
-Measurement time (0 - 60 min, default: 20 min)
-Test pressure (0 - 1500 hPa, default: 1000 hPa)
Pressure test 0 – 40 bar liquid gas:
-Stabilisation time (0 - 120 min, default: 10 min)
-Measurement time (1 - 240 min, default: 10 min)
-Test pressure (0 - 40 bar, default: 10 bar)
Each parameter can be adjusted the same way:
1. Select the parameter with cursor keys <up/down>
2. Press <Enter> to activate
3. Use numerical keys to input the value
To adjust the standard value press <F2>
Pressure check
Standard value : F2
10 min