Setting Via Tx1-Q20L60 Teach Adapter; Teach Adapter - Setting The Measuring Range; Teach Adapter - Resetting The Sensor To Factory Settings; Teach Adapter - Resetting The Sensor To Inverted Factory Settings - turck Li-Q25LxE Series Operating Instructions Manual

Linear position sensor with analog output
Table of Contents

Advertisement

9.2

Setting via TX1-Q20L60 teach adapter

9.2.1
Teach adapter – Setting the measuring range
Switch on the device power supply.
Place positioning element at the zero point of the measuring range.
Hold down the pushbutton on the adapter to Teach-Gnd for 2 s.
LED 2 flashes green for 2 s and then shows a continuous green light.
The zero point of the measuring range is stored.
Switch on the device power supply.
Place the positioning element at the end point of the measuring range.
Hold down the pushbutton on the adapter to Teach-UB for 2 s.
LED 2 flashes green for 2 s and then shows a continuous green light.
The end point of the measuring range is stored.
9.2.2
Teach adapter – Resetting the sensor to factory settings
Switch on the device power supply.
Hold down the pushbutton on the adapter to Teach-UB for 10 s.
LED 2 flashes green for 2 s,
then shows a continuous green light for 8 s
and flashes green again (after 10 s).
The sensor is reset to its factory settings.
9.2.3
Teach adapter – Resetting the sensor to inverted factory settings
Switch on the device power supply.
Hold down the pushbutton on the adapter to Teach-Gnd for 10 s.
LED 2 flashes green for 2 s,
then shows a continuous green light for 8 s
and flashes green again (after 10 s).
The sensor is reset to its inverted factory settings.
9.2.4
Teach adapter – Activating the Teach Lock
Switch on the device power supply.
Hold down the pushbutton on the adapter to Teach-UB for 30 s.
LED 2 first flashes green for 2 s,
then shows a continuous green light for 8 s
and flashes green again (after 10 s)
and then flashes green (after 30 s) at a higher frequency.
The Teach Lock function of the sensor is activated.
9.2.5
Teach adapter – Deactivating the Teach Lock
Switch on the device power supply.
Hold down the pushbutton on the adapter to Teach-UB for 30 s.
LED 2 shows a continuous green light for 30 s (Teach Lock is still activated)
and flashes green after 30 s at a higher frequency.
The Teach Lock function of the sensor is deactivated.
2018/10
NOTE
The Teach Lock function is deactivated by default.