Other documents ...................... 5 Feedback about these instructions................ 5 Notes on the Product ........................ 6 Product identification.................... 6 Scope of delivery ...................... 6 Turck service........................ 6 For Your Safety.......................... 7 Intended use........................ 7 Obvious misuse...................... 7 General safety instructions.................. 7 Product Description ........................
Page 4
Technical data – LUS211-…-2UPN8-H1141 ............ 33 14.2 Technical data – LUS211-…-4UPN8-H1181 ............ 35 14.3 Technical data – LUS211-…-LI2UPN8-H1141 ............ 37 15 Turck Subsidiaries - Contact Information ................. 39 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
This symbol denotes actions that the user must carry out. RESULTS OF ACTION This symbol denotes relevant results of actions. Other documents Besides this document the following material can be found on the Internet at www.turck.com: Data sheet Commissioning manual IO-Link devices IO-Link parameters manual...
CAD files in numerous export formats. The contact details of Turck subsidiaries worldwide can be found on p. [} 39]. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
The product is designed according to state-of-the-art technology. However, residual risks still exist. Observe the following warnings and safety notices to prevent damage to persons and property. Turck accepts no liability for damage caused by failure to observe these warning and safety notices.
Properties and features 4-digit, two-color 12-segment display, display rotatable by 180° Rotatable housing according to the mounting of the process connection G3/4" or NPT3/4" process connection Programmable NO/NC contact Process value transfer and parameterization via IO-Link Operating and display functions The front of the device is provided with three touchpads [ENTER], [MODE] and [SET], a 4-digit 12-segment multicolor display and status LEDs.
(LUS211-130…). If the upper limit value is changed, the lower limit value is automatically adjus- ted. tank level Hyst. Hyst. Fig. 3: Behavior of the switching output – Window function Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Hysteresis function The hysteresis function is used to teach in a stable switching state that is not affected by system-related fluctuations and the adjusted setpoint. The switching range is defined with a switching point and a reset point. The minimum hysteresis is 5 mm (LUS211-40…) and 10 mm (LUS211-130…).
More information on this is available from the Turck product database at www.turck.de/products in the Connectivity area. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Installing The sensor detects the surface of the medium nearest to the sensor and outputs the distance. The sensors can be installed in any alignment according to application requirements. The sound wave is propagated vertically to the sonic transducer at an opening angle of 15° (LUS211-40…) and 16°...
Burden at the analog output outside of the permissible range ErrT No object detected Short circuit Device locked uLoc Device unlocked - - - - Sensor failure Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Setting and Parameterization Settable functions and features Setting options via touchpads and IO-Link interface The following functions and properties can be set and used both in standard I/O mode as well as in IO-Link mode: Locking/unlocking the device Window function Hysteresis function Analog range Advanced settings:...
Release the touchpads when six green bars are flashing on the display. LOC LED goes out. uLoc appears in the display and goes out. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
9.2.3 Standard menu – overview Standard menu guidance – main menu Process value > 3 s Current value Save value SP1/FH1 rP1/FL1 > 3 s Current value Save value … Auto 4…20 … rtio SP2/FH2 rP2/FL2 > 3 s Current value ou3 (option) Save value SP3/FH3...
Page 20
FACT Current value > 3 s Software version VDMA Save value years OPHr days hours Fig. 15: EF extended functions menu Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
9.2.4 VDMA menu – overview VDMA menu – main menu Process value SP1/FH1 rP1/FL1 SP2/FH2/ASP rP2/FL2/AEP SP3/FH3 rP3/FL3 SP4/FH4 rP4/FL4 Fig. 16: VDMA main menu V01.00 | 2021/11...
Page 22
Save value > 3 s Software PASS version VDMA Save value years days hours OPHr Fig. 17: VDMA EF extended functions menu Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
9.2.5 Setting parameter values via touchpads Turck standard menu Unlock the device when [MODE] or [SET] is touched, a red running light appears and the LOC LED is lit. Touch [MODE] or [SET] until the required parameter is displayed.
Set value Set value hBot LnGt Set value Set value DToP FLAT DISH Set value hToP Set value Fig. 20: GEOM menu Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
9.2.7 Protecting the sensor with a password Select PASS in the EF menu. Change values via [SET]. Use [MODE] to navigate between the four digits of the password. Use [ENTER] to store the new password. > 3 s Gradually upwards (hex.) Pos.
Hysteresis function (NO = NO contact) Hysteresis function (NC = NC contact) Window function (NO = NO contact) Window function (NC = NC contact) Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Explanation Options Function Function of output 4 Hysteresis function (NO = NO contact) Hysteresis function (NC = NC contact) Window function (NO = NO contact) Window function (NC = NC contact) Submenu for additional See table “Parameters in the EF submenu” setting options 9.2.9 Parameters in the EF submenu (Extended Functions)
Page 28
(default in distance mode: 0.75 × measuring range) PASS Password protection Define password and activate password protection 0000 No password Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Explanation Options Function Reset FacT Reset the parameters to the factory settings Undo Reset the parameters to previous settings (last device start) Soft menu version Standard menu guidance VDMA VDMA menu guidance Operating hours counter Display of operating hours in years (y), days (d) and OPHr hours (h) 9.2.10 Parameters in the GEOM submenu (geometry)
All the parameters can be changed in IO-Link mode via the controller during commissioning as well as during operation. In SIO mode the device operates according to the last setting made in IO-Link mode. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Troubleshooting If the device does not function as expected, first check whether ambient interference is present. If there is no ambient interference present, check the connections of the device for faults. If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type.
Disposal The devices must be disposed of correctly and must not be included in general household garbage. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Technical Data 14.1 Technical data – LUS211-…-2UPN8-H1141 Technical data LUS211-40-…-2UPN8-H1141 LUS211-130-…-2UPN8-H1141 LUS211-40-51…: 100003163 LUS211-130-51…: 100003165 LUS211-40-34…: 100003164 LUS211-130-34…: 100003166 Function Ultrasonic diffuse mode senor Range 5…400 mm 130…1300 mm Resolution 0.5 mm 1 mm Minimum measuring range 50 mm 100 mm Minimum switching range 5 mm 10 mm...
Page 34
EN 61000-4-4 Burst: 2 kV EN 61000-4-6 HF line-conducted: 10 V EN 61000-4-5 1 kV, 42 Ω, Criterion B EN 61326-2-3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
14.2 Technical data – LUS211-…-4UPN8-H1181 Technical data LUS211-40-…-4UPN8-H1181 LUS211-130-…-4UPN8-H1181 LUS211-40-51…: 100003171 LUS211-130-51…: 100003173 LUS211-40-34…: 100003172 LUS211-130-34…: 100003174 Function Ultrasonic diffuse mode senor Range 5…400 mm 130…1300 mm Resolution 0.5 mm 1 mm Minimum measuring range 50 mm 100 mm Minimum switching range 5 mm 10 mm Ultrasonic frequency...
Page 36
EN 61000-4-4 Burst: 2 kV EN 61000-4-6 HF line-conducted: 10 V EN 61000-4-5 1 kV, 42 Ω, Criterion B EN 61326-2-3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 37
14.3 Technical data – LUS211-…-LI2UPN8-H1141 Technical data LUS211-40-…-LI2UPN8-H1141 LUS211-130-…-LI2UPN8-H1141 LUS211-40-51…: 100003167 LUS211-130-51…: 100003169 LUS211-40-34…: 100003168 LUS211-130-34…: 100003170 Function Ultrasonic diffuse mode senor Range 5…400 mm 130…1300 mm Resolution 0.5 mm 1 mm Minimum measuring range 50 mm 100 mm Minimum switching range 5 mm 10 mm Ultrasonic frequency...
Page 38
EN 61000-4-4 Burst: 2 kV EN 61000-4-6 HF line-conducted: 10 V EN 61000-4-5 1 kV, 42 Ω, Criterion B EN 61326-2-3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Turck Subsidiaries - Contact Information Germany Hans Turck GmbH & Co. KG Witzlebenstraße 7, 45472 Mülheim an der Ruhr www.turck.de Turck Australia Pty Ltd Australia Building 4, 19-25 Duerdin Street, Notting Hill, 3168 Victoria www.turck.com.au Belgium TURCK MULTIPROX Lion d'Orweg 12, B-9300 Aalst www.multiprox.be...
Page 40
Árpád fejedelem útja 26-28., Óbuda Gate, 2. em., H-1023 Budapest www.turck.hu Turck Inc. 3000 Campus Drive, USA-MN 55441 Minneapolis www.turck.us Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 41
Over 30 subsidiaries and over 60 representations worldwide! 100021492 | 2021/11 100021492 www.turck.com...