Contents About This Manual .......................... 5 Target groups........................ 5 Explanation of symbols used .................. 5 Other documents ...................... 5 Feedback about these instructions................ 5 Notes on the Product ......................... 6 Product identification..................... 6 Manufacturer and service .................... 6 Software-Supported IO-Link Parameterization................ 7 IO-Link Parameters..........................
Page 4
Contents Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
This symbol denotes actions that the user must carry out. RESULTS OF ACTION This symbol denotes relevant results of actions. Other documents Besides this document the following material can be found on the Internet at www.turck.com: Data sheet Quick Start Guide Operating instructions...
For further inquiries in Germany contact the Sales and Service Team on: Sales: +49 208 4952-380 Technology: +49 208 4952-390 Outside Germany, please contact your local Turck representative. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Using SIDI (Simple IO-Link Device Integration), IO-Link devices can be configured in PROFINET applications directly in the programming environment (e.g. TIA Portal). The Turck IO-Link devices are integrated in the GSDML file of the IO-Link masters in the TBEN, TBPN and FEN20 product series and can be configured in the programming environment as submodules of a modular I/O system.
Process input data Name Byte.Bit-offset Bit length Subindex access Data Type Value Description supported Process data False Integer -19999999… 134217727 134217721 Measurement value is filtered. 134217722 Sensor muted. 134217723 Value underrun 134217724 Value overrun 134217725 Geometry error 134217726 No target detected.
0x11 True read String www. Additional manufacturer (17) turck. information Product Name 0x12 True read String Manufacturer's device (18) designation Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 11
Name Index Sub- Subindex Access Byte. Data Type Value Default Description hex. index access Bit- length (dec.) hex. supported Offset (dec.) Product ID 0x13 True read String Ident-No. (19) Product Text 0x14 True read String Radar Device category (20) level sensor Serial Number 0x15 True...
0x53 True read/ UInteger 0…2 2 Switch polarity will be set auto- (83) write according to connected detection load. Auto Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 13
Name Index Sub- Subindex Access Byte. Data Type Value Default Description hex. index access Bit- length (dec.) hex. supported Offset (dec.) Measurement 0x54 False read/ UInteger 0…5 0 quantity (84) write Distance Distance % Level Level % Volume Volume % Length unit 0x54 False...
Page 14
Measured value ÷ 10000 = (Output 2) (97) write 9999 Value in unit … The values change if the 99999 unit is adjusted. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 15
Name Index Sub- Subindex Access Byte. Data Type Value Default Description hex. index access Bit- length (dec.) hex. supported Offset (dec.) Value at 0x69 True read Integer -1999 Measurement value at highest level (105) 9999 highest filling level … 13421 7727 13421 Value underrun...
Page 16
9999 … 99999 Lower edge of 0x88 False read/ 26.0 28 Integer -1999 cone (136) write 9999 … 99999 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 17
Select the type of the menu (143) write sensors menu structure. The type of operator menu is retained after the reset to the factory setting. Turck standard menu VDMA menu Signal 0x90 True read/ UInteger 0…3 0 Filter signals with...
Page 18
On switching delay/ switching delay at FH1 Off switching delay/ switching delay at FL2 Geometry Display unit Custom geometry: Height nodes Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 19
Name Index Sub- Subindex Access Byte. Data Type Value Default Description hex. index access Bit- length (dec.) hex. supported Offset (dec.) Custom geometry: Volume nodes Dynamic blindzone Menu mode Intensity filter mode Filter: Max. amplitude Filter: Min. amplitude Frontground suppression Background suppression Error message 0xA8 True...
Page 20
Minimum value for signal amplitude filter is to small. Minimum value for signal amplitude filter is to large. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 21
Name Index Sub- Subindex Access Byte. Data Type Value Default Description hex. index access Bit- length (dec.) hex. supported Offset (dec.) Minimum value for signal amplitude filter is to close the maximum filter value. Maximum value for signal amplitude filter is to small. Maximum value for signal amplitude filter is to large.