How to Install
3.7.4 Potentiometer Reference
Voltage reference via a potentiometer
Reference Source 1 = [1] Analog input 53 (default)
Terminal 53, Low Voltage = 0 V
Terminal 53, High Voltage = 10 V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
Speed RPM
P 6-15
Ref. voltage
P 6-11 10V
Illustration 3.88 Potentiometer Reference

3.8 Final Set-up and Test

To test the set-up and ensure that the frequency converter
is running, follow these steps.
Step 1. Locate the motor name plate
NOTICE
The motor is either star- (Y) or delta- connected (Δ). This
information is located on the motor name plate data.
VLT AQUA Drive FC 202 Operation Instructions
39 42
50
53 54
55
1 k
Step 2. Enter the motor name plate data in this
parameter list.
To access this list first press [Quick Menu] then select "Q2
Quick Setup".
1.
2.
3.
4.
5.
Step 3. Activate the Automatic Motor Adaptation (AMA)
Performing an AMA ensures optimum performance. The
AMA measures the values from the motor model
equivalent diagram.
MG20P402 - Rev. 2013-12-16
THREE PHASE INDUCTION MOTOR
MOD MCV 315E
Nr.
135189 12 04
kW
400
PRIMARY
HP
536
V 690
A
410.6
mm 1481
V
A
Hz
50
V
A
DESIGN
N
SECONDARY
DUTY
S1
V
A
INSUL
I
EFFICIENCY % 95.8%
100%
CAUTION
Illustration 3.89
1-20 Motor Power [kW]
1-21 Motor Power [HP]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
Table 3.49
1.
Connect terminal 37 to terminal 12 (if terminal 37
is available).
2.
Connect terminal 27 to terminal 12 or set
5-12 Terminal 27 Digital Input to [0] No function.
3.
Activate the AMA 1-29 Automatic Motor
Adaptation (AMA).
4.
Select between complete or reduced AMA. If a
Sine-wave filter is mounted, run only the reduced
AMA, or remove the Sine-wave filter during the
AMA procedure.
IL/IN 6.5
SF
1.15
CONN Y
COS f
0.85
40
CONN
°C
AMB 40
ALT
1000
m
CONN
RISE
°C
80
CONN
ENCLOSURE
IP23
95.8% 75%
WEIGHT
1.83 ton
67
3
3