General Specifications
Mains Supply 3x380-480 V AC
Typical Shaft output at
400 V [kW]
Typical Shaft output at
460 V [hp]
Enclosure IP21
Enclosure IP54
Enclosure IP00
Output current
Continuous
(at 400 V) [A]
Intermittent (60 s
overload)
(at 400 V) [A]
Continuous
(at 460/480 V) [A]
Intermittent (60 s
overload)
(at 460/480 V) [A]
Continuous KVA
(at 400 V) [KVA]
Continuous KVA
(at 460 V) [KVA]
Max. input current
Continuous
(at 400 V) [A]
Continuous
(at 460/480 V) [A]
Max. cable size, mains
motor, brake and load
share [mm
2
(AWG
2)
)]
Max. external pre-fuses
1
[A]
Estimated power loss
at rated max. load [W]
4)
,
400 V
Estimated power loss
4)
at rated max. load [W]
,
460 V
Weight,
enclosure IP21, IP54 [kg]
Weight,
enclosure IP00 [kg]
4)
Efficiency
Output frequency
Heat sink overtemp. trip
Power card ambient trip
Table 6.1
VLT AQUA Drive FC 202 Operation Instructions
P110
P132
110
132
150
200
D1
D1
D1
D1
D3
D3
212
260
233
286
190
240
209
264
147
180
151
191
204
251
183
231
2x70
2x70
(2x2/0)
(2x2/0)
300
350
3234
3782
2947
3665
96
104
82
91
90 °C
110°C
MG20P402 - Rev. 2013-12-16
P160
P200
160
200
250
300
D2
D2
D2
D2
D4
D4
315
395
347
435
302
361
332
397
218
274
241
288
304
381
291
348
2x150
2x150
(2x300 mcm)
(2x300 mcm)
400
500
4213
5119
4063
4652
125
136
112
123
0.98
0-800 Hz
110 °C
110°C
60 °C
P250
250
350
D2
D2
D4
480
528
6
6
443
487
333
353
463
427
2x150
(2x300 mcm)
630
5893
5634
151
138
110°C
121

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc 200 series