Danfoss VLT AQUA FC 202 Operating Instructions Manual page 110

Hide thumbs Also See for VLT AQUA FC 202:
Table of Contents

Advertisement

How to programme the freque...
22-83 Speed at No-Flow [RPM]
Range:
Size
[ 0 -
related
par.
*
22-85
RPM]
5
5
22-84 Speed at No-Flow [Hz]
Range:
Size
[ 0 -
related
par.
*
22-86
Hz]
22-85 Speed at Design Point [RPM]
Range:
Size
[ 0 -
related
60000
*
RPM]
22-86 Speed at Design Point [Hz]
Range:
Size
[ 0.0 -
related
par.
*
4-19
Hz]
108
VLT AQUA Drive FC 202 Operation Instructions
Function:
Resolution 1 RPM.
The speed of the motor at which flow Is
zero and minimum pressure H
MIN
should be entered here in RPM. Alterna-
tively, the speed in Hz can be entered in
parameter 22-84 Speed at No-Flow [Hz]. If it
has been decided to use RPM in 0-02 Motor
Speed Unit then parameter 22-85 Speed at
Design Point [RPM] should also be used.
Closing the valves and reducing the speed
until minimum pressure H
is achieved
MIN
determines this value.
Function:
Resolution 0.033 Hz.
The speed of the motor at which flow has
effectively stopped and minimum pressure
H
is achieved should be entered here in
MIN
Hz. Alternatively, the speed in RPM can be
entered in parameter 22-83 Speed at No-Flow
[RPM]. If it has been decided to use Hz in
0-02 Motor Speed Unit then
parameter 22-86 Speed at Design Point [Hz]
should also be used. Closing the valves and
reducing the speed until minimum pressure
H
is achieved determines this value.
MIN
Function:
Resolution 1 RPM.
Only visible when parameter 22-82 Work
Point Calculation is set to Disable. The
speed of the motor at which the System
Design Working Point is achieved should
be entered here in RPM. Alternatively, the
speed in Hz can be entered in
parameter 22-86 Speed at Design Point [Hz].
If it has been decided to use RPM in
0-02 Motor Speed Unit then
parameter 22-83 Speed at No-Flow [RPM]
should also be used.
Function:
Resolution 0.033 Hz.
Only visible when parameter 22-82 Work
Point Calculation is set to Disable. The speed
of the motor at which the System Design
Working Point is achieved should be
entered here in Hz. Alternatively, the speed
in RPM can be entered in
parameter 22-85 Speed at Design Point [RPM].
22-86 Speed at Design Point [Hz]
Range:
is achieved
22-87 Pressure at No-Flow Speed
Range:
0
[ 0 - par. 22-88 ] Enter the pressure H
*
Also see parameter 22-82 Work Point Calculation point D.
22-88 Pressure at Rated Speed
Range:
999999.999
*
999999.999 ]
Also see parameter 22-82 Work Point Calculation point C.
22-90 Flow at Rated Speed
Range:
0
[0 - 999999.999 ] Enter the value corresponding to Flow at
*
5.2.10 23-0* Timed Actions
Use Timed Actions for actions needing to be performed on
a daily or weekly basis, e.g. different references for working
hours/non-working hours. Up to 10 Timed Actions can be
programmed in the frequency converter. The Timed Action
number is selected from the list when entering parameter
group 23-0* from the LCP. Parameter 23-00 ON Time –
parameter 23-04 Occurrence then refer to the selected
Timed Action number. Each Timed Action is divided into
an ON time and an OFF time, in which 2 different actions
may be performed.
The clock control (parameter group 0-7* Clock Settings) of
Timed Actions can be overridden from Timed Actions Auto
(Clock Controlled) to Timed Actions Disabled, Constant OFF
Actions or Constant ON Actions either in 23-08 Timed
Actions Mode or with commands applied to the digital
inputs ([68] Timed Actions Disabled, [69] Constant OFF
Actions or [70] Constant ON Actions, in parameter group
5-1* Digital Inputs.
MG20P402 - Rev. 2013-12-16
Function:
If it has been decided to use Hz in
0-02 Motor Speed Unit, then
parameter 22-83 Speed at No-Flow [RPM]
should also be used.
Function:
corresponding to
MIN
Speed at No Flow in Reference/Feedback
Units.
Function:
[ par. 22-87 -
Enter the value corresponding
to the Pressure at Rated Speed,
in Reference/Feedback Units.
This value can be defined using
the pump datasheet.
Function:
Rated Speed. This value can be defined
using the pump datasheet.