How to programme the freque...
22-31 Power Correction Factor
Range:
Function:
100
[1 -
Make corrections to the calculated power at
%
400 %]
parameter 22-30 No-Flow Power.
*
If No Flow is detected, when it should not be
detected, decrease the setting. However, if No
Flow is not detected, when it should be
detected, increase the setting to above 100%.
22-32 Low Speed [RPM]
Range:
Function:
Size
[ 0 - par.
To be used if 0-02 Motor Speed Unit has
related
22-36 RPM]
been set for RPM (parameter not visible
*
if Hz selected).
Set used speed for the 50% level.
This function is used for storing values
needed to tune No Flow Detection.
22-33 Low Speed [Hz]
Range:
Function:
Size
[ 0 - par.
To be used if 0-02 Motor Speed Unit has
related
22-37 Hz]
been set for Hz (parameter not visible if
*
RPM selected).
Set used speed for the 50% level.
The function is used for storing values
needed to tune No Flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
Size
[ 0 -
To be used if 0-03 Regional Settings has
related
5.50 kW]
been set for International (parameter not
*
visible if North America selected).
Set power consumption at 50% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
22-35 Low Speed Power [HP]
Range:
Function:
Size
[ 0 -
To be used if 0-03 Regional Settings has
related
7.50 hp]
been set for North America (parameter
*
not visible if International selected).
Set power consumption at 50% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range:
Function:
Size
[ 0 - par.
To be used if 0-02 Motor Speed Unit has
related
4-13 RPM]
been set for RPM (parameter not visible
*
if Hz selected).
Set used speed for the 85% level.
The function is used for storing values
needed to tune No Flow Detection.
VLT AQUA Drive FC 202 Operation Instructions
22-37 High Speed [Hz]
Range:
Size
related
*
22-38 High Speed Power [kW]
Range:
Size
related
*
22-39 High Speed Power [HP]
Range:
Size
related
*
22-40 Minimum Run Time
Range:
60 s
*
22-41 Minimum Sleep Time
Range:
30 s
*
22-42 Wake-up Speed [RPM]
Range:
Size
related
*
MG20P402 - Rev. 2013-12-16
Function:
[ 0 - par.
To be used if 0-02 Motor Speed Unit has
4-14 Hz]
been set for Hz (parameter not visible if
RPM selected).
Set used speed for the 85% level.
The function is used for storing values
needed to tune No Flow Detection.
Function:
[ 0 -
To be used if 0-03 Regional Settings has
5.50 kW]
been set for International (parameter not
visible if North America selected).
Set power consumption at 85% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
Function:
[ 0 -
To be used if 0-03 Regional Settings has
7.50 hp]
been set for North America (parameter
not visible if International selected).
Set power consumption at 85% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
Function:
[0 - 600 s] Set the desired minimum running time for
the motor after a start command (digital
input or Bus) before entering Sleep Mode.
Function:
[0 - 600 s] Set the desired Minimum Time for staying in
Sleep Mode. This overrides any wake up
conditions.
Function:
[ 0 -
To be used if 0-02 Motor Speed Unit has
par.
been set for RPM (parameter not visible if
4-13
Hz selected). Only to be used if
RPM]
parameter 1-00 Configuration Mode is set for
open loop and speed reference is applied
by an external controller.
Set the reference speed at which the Sleep
Mode should be cancelled.
5
5
105