Danfoss VLT AQUA FC 202 Operating Instructions Manual page 127

Hide thumbs Also See for VLT AQUA FC 202:
Table of Contents

Advertisement

General Specifications
Mains Supply 3x525-690 V AC
Typical Shaft output at 550 V
[kW]
Typical Shaft output at 575 V
[HP]
Typical Shaft output at 690 V
[kW]
Enclosure IP21
Enclosure IP54
Enclosure IP00
Output current
Continuous
(at 550 V) [A]
Intermittent (60 sec overload)
(at 550 V) [A]
Continuous
(at 575/ 690 V) [A]
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
Continuous KVA
(at 550 V) [KVA]
Continuous KVA
(at 575 V) [KVA]
Continuous KVA
(at 690 V) [KVA]
Max. input current
Continuous
(at 550 V ) [A]
Continuous
(at 575 V) [A]
Continuous
(at 690 V) [A]
Max. cable size, mains motor,
load share and brake [mm
2
(AWG)]
1
Max. external pre-fuses [A]
Estimated power loss
4)
at rated max. load [W]
, 600 V
Estimated power loss
at rated max. load [W]
4)
, 690 V
Weight,
Enclosure IP21, IP 54 [kg]
Weight,
Enclosure IP00 [kg]
4)
Efficiency
Output frequency
Heat sink overtemp. trip
Power card ambient trip
Table 6.5
VLT AQUA Drive FC 202 Operation Instructions
P132
110
150
132
D1
D1
D3
162
178
155
171
154
154
185
158
151
155
2 x 70 (2 x 2/0)
2 x 70 (2 x 2/0)
315
2963
3430
96
82
90 °C
110°C
MG20P402 - Rev. 2013-12-16
P160
P200
132
160
200
250
160
200
D1
D2
D1
D2
D3
D4
201
253
221
278
192
242
211
266
191
241
191
241
229
289
198
245
189
234
197
240
2 x 150 (2 x 300 mcm) 2 x 150 (2 x 300 mcm)
350
350
3430
4051
3612
4292
104
125
91
112
0.98
0 - 600 Hz
110 °C
60 °C
P250
200
300
250
D2
D2
D4
303
6
6
333
290
319
289
289
347
299
286
296
400
4867
5156
136
123
110 °C
125

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc 200 series