How to programme the freque...
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999 ]
6-25 Terminal 54 High Ref./Feedb. Value
Range:
100
[-999999.999 -
*
5
5
999999.999 ]
6-50 Terminal 42 Output
Option:
[0]
No operation
[100] Output freq. 0-100
[101] Reference Min-Max
[102] Feedback +-200%
[103] Motor cur. 0-Imax
[104] Torque 0-Tlim
[105] Torque 0-Tnom
[106] Power 0-Pnom
[107] Speed 0-HighLim
[108] Torque +-160%
[109] Out frq 0-Fmax
[113] Ext. Closed Loop 1
[114] Ext. Closed Loop 2
[115] Ext. Closed Loop 3
[116] Cascade Reference
[130] Out frq 0-100
4-20mA
[131] Reference 4-20mA
[132] Feedback 4-20mA
100
VLT AQUA Drive FC 202 Operation Instructions
Function:
Enter the analog input scaling value that
corresponds to the low voltage/low
current value set in
parameter 6-20 Terminal 54 Low Voltage
and 6-22 Terminal 54 Low Current.
Function:
Enter the analog input scaling value
that corresponds to the high voltage/
high current value set in
parameter 6-21 Terminal 54 High
Voltage and 6-23 Terminal 54 High
Current.
Function:
Select the function of Terminal 42 as
an analog current output. A motor
current of 20 mA corresponds to I
0-100 Hz, (0-20 mA)
Minimum reference - Maximum
reference, (0-20 mA)
-200% to +200% of 20-14 Maximum
Reference/Feedb., (0-20 mA)
0 - Inverter Max. Current (16-37 Inv.
Max. Current), (0-20 mA)
0 - Torque limit (4-16 Torque Limit
Motor Mode), (0-20 mA)
0 - Motor rated torque, (0-20 mA)
0 - Motor rated power, (0-20 mA)
0 - Speed High Limit
(parameter 4-13 Motor Speed High
Limit [RPM] and 4-14 Motor Speed
High Limit [Hz]), (0-20 mA)
0-100%, (0-20 mA)
0-100%, (0-20 mA)
0-100%, (0-20 mA)
0-100 Hz
Minimum Reference - Maximum
Reference
-200% to +200% of 20-14 Maximum
Reference/Feedb.
MG20P402 - Rev. 2013-12-16
6-50 Terminal 42 Output
Option:
[133] Motor cur. 4-20mA
[134] Torq.0-lim 4-20 mA
[135] Torq.0-nom 4-20mA 0 - Motor rated torque
[136] Power 4-20mA
[137] Speed 4-20mA
[138] Torque 4-20mA
[139] Bus ctrl.
[140] Bus ctrl. 4-20 mA
[141] Bus ctrl t.o.
[142] Bus ctrl t.o. 4-20mA
[143] Ext. CL 1 4-20mA
[144] Ext. CL 2 4-20mA
[145] Ext. CL 3 4-20mA
.
[146] Cascade Ref.
max
4-20mA
[147] Main act val
0-20mA
[148] Main act val
4-20mA
[150] Out frq 0-Fmax
4-20mA
[254] DC Link 0-20mA
[255] DC Link 4-20mA
NOTICE
Values for setting the Minimum Reference is found in
open loop parameter 3-02 Minimum Reference and for
closed loop 20-13 Minimum Reference/Feedb. - values for
maximum reference for open loop is found in
3-03 Maximum Reference and for closed loop
20-14 Maximum Reference/Feedb.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0 %
[0 - 200
Scale for the minimum output (0 or 4 mA) of
*
%]
the analog signal at terminal 42.
Set the value to be the percentage of the full
range of the variable selected in
parameter 6-50 Terminal 42 Output.
Function:
0 - Inverter Max. Current (16-37 Inv.
Max. Current)
0 - Torque limit (4-16 Torque Limit
Motor Mode)
0 - Motor rated power
0 - Speed High Limit (4-13 and 4-14)
0-100%, (0-20 mA)
0-100%
0-100%, (0-20 mA)
0-100%
0-100%
0-100%
0-100%